Carrier 38AH044-084 specifications Field-supplied NOTES

Models: 38AH044-084

1 56
Download 56 pages 61.81 Kb
Page 36
Image 36
Manual background

*Field-supplied.

NOTES:

1.

Factory wiring is in accordance with NEC. Field modi®cations or

 

additions must be in compliance with all applicable codes.

2.

Wiring for ®eld power supply must be rated 75 C minimum. Use

 

copper, copper-clad aluminum, or aluminum conductors. Maxi-

 

mum incoming wire size for each terminal block is 500 kcmil.

3.

Terminal blocks TB3 and TBX1 are for external ®eld control con-

 

nections. Control connections are to be Class 1 wiring.

4.

Field-supplied components (IFC, LLS-A1 and A2) must have a maxi-

LEGEND

 

mum sealed coil rating of 30 va each (0.25 amp at 120 vac,

 

0.13 amp at 230 vac). AHMS IFC-AUX contact must have mini-

 

mum pilot duty rating of 400 va each (3.4 amps at 120 vac,

 

1.8 amps at 230 vac).

5.

Replacement of factory wires must be with type 105 C wire or its

 

equivalent.

6.

Field-supplied liquid line solenoid valves installed at the evapora-

 

tor are required on all units.

7.

Units have 175 va of power available for ®eld-installed

 

accessories.

AHMS Ð Air Handler Motor Starter

AUX Ð Auxilliary

CÐ Compressor Contactor

FU Ð Fuse

GND

Ð Equipment Ground

IFC

Ð

Indoor Fan Control

kcmil

Ð

Thousand Circular Mils

LLS

Ð

Liquid Line Solenoid

NEC

Ð National Electrical Code

 

 

(U.S.A. Standard)

SDR

Ð Solenoid Drop Relay

TB

Ð Terminal Block

TBX

Ð Terminal Block for Variable

TM

Air Volume Units

Ð Timer Motor

TR

Ð Timer Relay

TRAN Ð Transformer

UÐ Unloader Solenoid

Factory Wiring Field Wiring

Fig. 28 Ð Field Wiring, Single ModuPanel™ Control, Units 38AH124 and 134

36