38AH

*To control heating device and provide automatic indoor- fan operation on heating.

²Jumper removed only when separate 24-v trans- former power source is used to power the 33CSUCE-06 relay pack.

**Field-supplied.

NOTES:

Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.

1.Liquid line solenoid valve LLS-A1 is used for solenoid drop on circuit A. Liquid line solenoid valve LLS-B1 is used for solenoid drop for circuit B.

2.Solenoid drop is a safety feature which prevents refrigerant migration to the compressor during the OFF cycle. It is rec- ommended on all systems and required on systems where piping exceeds 75 ft (22.9 m) in length.

3.The 33CSUCE-06 relay pack requires 10 va.

4.Factory wiring is in accordance with NEC; ®eld modi®cations or additions must be in compliance with all applicable codes.

5.Wiring for ®eld power supply must be rated 75 C mini- mum. Use copper, copper-clad aluminum, or aluminum con- ductors. Maximum incoming wire size for each terminal block is 500 kcmil.

6.Terminal blocks are for external ®eld control connections. Con- trol connections must be Class 1 wiring.

7.Field-supplied components (IFC, LLS-A1, and LLS-B1) must have a maximum sealed coil rating of 30 va each (0.25 amp at 120 vac and 0.13 amp at 230 vac). Thermostats must have a minimum pilot duty rating as follows:

38AH

VA

AMPS

VAC

(Ea Stage)

 

 

 

094

275

2.29

120

1.15

240

 

 

104

325

2.70

120

1.35

240

 

 

8.Replacement of factory wires must be with type 105 C wire or its equivalent.

9.Field-supplied liquid line solenoid valves in- stalled at the evaporator are required on all units.

10.Units 38AH094 has 140 va and unit 38AH104 has 130 va of power available for ®eld- installed accessories.

11.To minimize voltage drop, the following wire sizes are recommended:

LENGTH Ð

INSULATED WIRE Ð

AWG

Ft (M)

(35 C Minimum)

 

Up to 50

No. 18

(15.2)

 

50-75

No. 16

(15.2-22.9)

 

More Than 75

No. 14

(22.9)

 

 

 

LEGEND

AWG

Ð American Wire Gage

CR

Ð Control Relay

HD

Ð Heating Device

IFC

Ð

Indoor-Fan Contactor

IFR

Ð

Indoor-Fan Relay

kcmil

Ð

Thousand Circular Mils

LLS

Ð

Liquid Line Solenoid

NEC

Ð National Electrical Code

 

 

(U.S.A. Standard)

RÐ Heating Relay (®eld- supplied 24-v sealed coil,

RV

Ð

10 va maximum rating)

Reversing Valve

TB

Ð

Terminal Block

 

 

Factory Wiring

 

 

Field Wiring

Fig. 22 Ð Field Wiring, One 2-Stage Thermostat Ð Units 38AH094 and 104