Carrier 38AH044-084 specifications Optional Single-Circuitunit

Models: 38AH044-084

1 56
Download 56 pages 61.81 Kb
Page 24
Image 24

Table 10B Ð Electrical Data Ð 50/60 Hz (38AH044-084 Optional Single-Circuit Units)

 

 

OPTIONAL SINGLE-CIRCUIT UNIT

 

 

 

 

 

COMPRESSOR*

 

 

Voltage

Compressor

Nameplate

Supply Voltage

 

 

 

A1

A2

 

38AH

A1/A2

 

 

 

MCA

MOCP

ICF

 

 

 

 

 

 

Designation

Model No.

V-Ph-Hz

Min

 

Max

 

 

 

RLA

LRA

RLA

 

LRA

 

 

 

 

 

 

 

 

 

500

 

208/230-3-60

187

 

254

179.4

225

434.7

67.9

345

67.9

 

345

 

600

 

460-3-60

414

 

508

91.3

100

218.6

34.6

173

34.6

 

173

044

100

 

575-3-60

518

 

632

78.4

100

162.4

28.8

120

28.8

 

120

200

06E4250/250

380-3-60

342

 

418

93.5

125

241.2

34.6

191

34.6

 

191

 

800 (PW)

 

230-3-50

198

 

254

180.2

225

296.7

67.9

207

67.9

 

207

 

900

 

380/415-3-50

342

 

440

91.5

100

219.6

34.6

173

34.6

 

173

 

300 (PW)

 

346-3-50

325

 

367

100.0

125

165.9

33.3

115

33.3

 

115

 

500

 

208/230-3-60

187

 

254

206.6

250

535.7

89.7

446

67.9

 

345

 

600

 

460-3-60

414

 

508

102.4

125

268.6

43.6

223

34.6

 

173

054

100

06E4265/250

575-3-60

518

 

632

88.0

125

206.4

36.5

164

28.8

 

120

200

380-3-60

342

 

418

107.1

150

297.2

45.5

247

34.6

 

191

 

 

 

 

 

900

 

380/415-3-50

342

 

440

102.7

125

269.6

43.6

223

34.6

 

173

 

300 (PW)

 

346-3-50

325

 

367

107.0

150

198.9

44.9

148

33.3

 

115

 

500

 

208/230-3-60

187

 

254

249.3

350

617.5

106.4

506

89.7

 

446

 

600

 

460-3-60

414

 

508

115.5

150

307.6

46.8

253

43.6

 

223

064

100

06E8275/265

575-3-60

518

 

632

100.6

125

226.1

40.4

176

36.5

 

164

200

380-3-60

342

 

418

126.9

175

341.1

52.6

280

45.5

 

247

 

 

 

 

 

900

 

380/415-3-50

342

 

440

115.7

150

335.6

46.8

280

43.6

 

223

 

300 (PW)

 

346-3-50

325

 

367

129.8

175

230.5

53.8

168

44.9

 

148

 

500

 

208/230-3-60

187

 

254

330.5

450

829.0

147.4

690

106.4

 

506

 

600

 

460-3-60

414

 

508

148.6

200

408.2

65.4

345

46.8

 

253

074

100

06E8299/275

575-3-60

518

 

632

132.2

175

336.8

57.1

276

40.4

 

176

200

380-3-60

342

 

418

174.5

250

458.0

78.8

382

52.6

 

280

 

 

 

 

 

900

 

380/415-3-50

342

 

440

143.0

200

403.8

65.4

345

46.8

 

280

 

300 (PW)

 

346-3-50

325

 

367

170.8

250

300.4

79.5

229

53.8

 

168

 

500

 

208/230-3-60

187

 

254

371.5

500

870.0

147.4

690

147.4

 

690

 

600

 

460-3-60

414

 

508

167.2

225

426.8

65.4

345

65.4

 

345

084

100

06E8299/299

575-3-60

518

 

632

148.9

200

353.5

57.1

276

57.1

 

276

200

380-3-60

342

 

418

200.7

250

484.2

78.8

382

78.8

 

382

 

 

 

 

 

900

 

380/415-3-50

342

 

440

167.6

225

428.4

65.4

345

65.4

 

345

 

300 (PW)

 

346-3-50

325

 

367

205.3

250

334.9

79.5

229

79.5

 

229

 

 

LEGEND

FLA

Ð Full Load Amps

ICF

Ð Maximum Instantaneous Current Flow During Starting.

 

 

(The point in the starting sequence where the sum of

 

 

the LRA for the starting compressors, plus the total RLA

 

 

for all running compressors, plus the FLA for all running

kcmil

Ð

fan motors is maximum.)

Thousand Circular Mils

LRA

Ð Locked Rotor Amps

Max

Ð Maximum

MCA

Ð Minimum Circuit Amps (used for sizing; complies with

 

 

National Electrical Code [NEC] [U.S.A. Standard],

Min

Ð

section 430-24).

Minimum

MOCP Ð Maximum Overcurrent Protection (used for sizing dis-

 

connect; complies with NEC Article 440, Section 22).

RLA

Ð Rated Load Amps

PW

Ð Part Wind Only

*All compressors are across-the-line start only except 38AH044 230 v, 3-phase, 50 Hz; and all 346 v, 3-phase, 50 Hz.

²Units are suitable for use on electrical systems where voltage sup- plied to unit terminals is within listed minimum to maximum limits.

NOTES:

1.Maximum allowable phase imbalance: voltage - 2%; amps - 10%.

2.Maximum incoming wire size for terminal block is 500 kcmil.

24