Carrier 38AH044-084 specifications Ð Unit Control Box, Ð Condenser Fan Adjustment

Models: 38AH044-084

1 56
Download 56 pages 61.81 Kb
Page 51
Image 51
Fig. 48 Ð Unit Control Box

 

TRANSFORMERS

 

TIMERS

 

 

 

TIME-DELAY

 

 

 

RELAY

 

 

 

OIL PRESSURE

FUSE

TERMINAL

COMPRESSOR

SWITCHES

HOLDERS

BLOCKS

CONTACTORS

Fig. 48 Ð Unit Control Box

FAN CONTACTORS

COMPRESSOR CIRCUIT BREAKERS

FAN CIRCUIT

BREAKER

TERMINAL

BLOCKS

Required Compressor Modi®cation for 38AH044- 084 Optional Single-Circuit Units, When Com- pressor A1 is Out Ð To maintain unit operation, com- pressor no.1 must be operable. If it is not operable, the following temporary modi®cations must be made to keep the unit running:

1.

Change the oil pressure switch connections from com-

 

pressor A1 to compressor A2.

2.

Connect compressor A2 into the Time Guard circuit as

 

compressor A1 was originally.

3.

Open compressor A1 circuit breaker.

NOTE: Make sure the crankcase heaters are energized when compressors are off.

NOTE: Fan rotation is clockwise when viewed from top of unit.

Fig. 49 Ð Condenser Fan Adjustment

51