Remove sheet metal cover panels from
IMPORTANT: Modules must be placed 24 in. (610 mm) apart and square relative to each other.
The modules are now in position for piping installa- tion and ®nal assembly. See Fig. 8. For mounting units on vibration isolators, a perimeter support channel is required between the assembled unit and the support isolators. The perimeter support channel must be sized to support the fully assembled unit. Do not support modules on individual iso- lation supports. Support channel, hardware, and fasteners are ®eld supplied.
When unit is in proper location, level unit and bolt into position with
Table 2A Ð Operational Corner Weights with
Refrigerant Charge (Approximate) Ð Lb
UNIT |
| TOTAL | OPERATIONAL CORNER WEIGHT | |||
38AH |
| WEIGHT | A | B | C | D |
044 |
| 3259 | 939 | 893 | 695 | 732 |
044C |
| 3547 | 1013 | 967 | 765 | 802 |
054 |
| 3309 | 964 | 905 | 697 | 742 |
054C |
| 3597 | 1034 | 978 | 771 | 814 |
064 |
| 3565 | 1018 | 1011 | 765 | 771 |
064C |
| 3998 | 1125 | 1117 | 874 | 879 |
074 |
| 3812 | 1146 | 986 | 777 | 903 |
074C |
| 4229 | 1272 | 1059 | 862 | 1035 |
084 |
| 4057 | 1220 | 1049 | 827 | 961 |
084C |
| 4735 | 1425 | 1186 | 965 | 1159 |
094 |
| 5088 | 1114 | 2192 | 1182 | 601 |
094C |
| 5813 | 1273 | 2504 | 1350 | 686 |
104 |
| 5435 | 1240 | 2138 | 1302 | 755 |
104C |
| 6160 | 1405 | 2423 | 1476 | 856 |
MODULE |
|
|
|
|
| |
38AH |
|
|
|
|
| |
124A |
| 3630 | 1037 | 1030 | 779 | 785 |
| 4063 | 1144 | 1137 | 889 | 894 | |
124B |
| 3630 | 1037 | 1030 | 779 | 785 |
| 4063 | 1144 | 1137 | 889 | 894 | |
134A |
| 3630 | 1037 | 1030 | 779 | 785 |
| 4063 | 1144 | 1137 | 889 | 894 | |
134B |
| 3877 | 1167 | 997 | 789 | 924 |
| 4294 | 1293 | 1080 | 874 | 1047 | |
|
|
|
|
|
|
|
LEGEND
C Ð Copper Fin Coils
NOTE: Total weight may differ from summation of corner weights due to rounding of numerals.
Step 2 Ð Check Compressor Mounting
UNITS
UNITS
Units 38AH124 and 134 compressors are mounted on pans and are held down by 4 bolts during shipment. After unit is installed, loosen each of these bolts until snubber washer can be moved with ®nger pressure. See Fig. 10.
Table 2B Ð Operational Corner Weights with
Refrigerant Charge (Approximate) Ð Kg
UNIT |
| TOTAL | OPERATIONAL CORNER WEIGHT | |||
38AH |
| WEIGHT | A | B | C | D |
044 |
| 1478 | 426 | 405 | 316 | 332 |
044C |
| 1609 | 460 | 438 | 347 | 364 |
054 |
| 1501 | 437 | 411 | 316 | 337 |
054C |
| 1632 | 469 | 444 | 350 | 369 |
064 |
| 1617 | 462 | 459 | 347 | 350 |
064C |
| 1813 | 510 | 508 | 397 | 399 |
074 |
| 1729 | 520 | 447 | 352 | 410 |
074C |
| 1918 | 577 | 481 | 391 | 470 |
084 |
| 1840 | 553 | 476 | 375 | 436 |
084C |
| 2148 | 646 | 538 | 438 | 526 |
094 |
| 2308 | 505 | 994 | 536 | 272 |
094C |
| 2637 | 577 | 1136 | 612 | 311 |
104 |
| 2465 | 562 | 970 | 591 | 342 |
104C |
| 2794 | 637 | 1099 | 670 | 388 |
MODULE |
|
|
|
|
| |
38AH |
|
|
|
|
| |
124A |
| 1647 | 470 | 467 | 353 | 356 |
| 1843 | 519 | 516 | 403 | 405 | |
124B |
| 1647 | 470 | 467 | 353 | 356 |
| 1843 | 519 | 516 | 403 | 405 | |
134A |
| 1647 | 470 | 467 | 353 | 356 |
| 1843 | 519 | 516 | 403 | 405 | |
134B |
| 1759 | 529 | 452 | 358 | 419 |
| 1948 | 587 | 490 | 396 | 475 | |
|
|
|
|
|
|
|
LEGEND
C Ð Copper Fin Coils
NOTE: Total weight may differ from summation of corner weights due to rounding of numerals.
TOP VIEW, TYPICAL
3