Carrier 38AH044-084 specifications Field-supplied NOTES

Models: 38AH044-084

1 56
Download 56 pages 61.81 Kb
Page 34
Image 34
Manual background

*Field-supplied.

NOTES:

1.

Factory wiring is in accordance with NEC. Field modi®cations

 

or additions must be in compliance with all applicable codes.

2.

Wiring for ®eld power supply must be rated 75 C minimum. Use

 

copper, copper-clad aluminum, or aluminum conductors. Maxi-

 

mum incoming wire size for each terminal block is 500 kcmil.

3.

Terminal blocks TB3, TB4, TBX1, and TBX2 are for external

 

®eld control connections. Control connections are to be

 

Class 1 wiring.

LEGEND

4.

Field-supplied components (IFC, LLS-A1, A2, B1, and B2) must

 

have a maximum sealed coil rating of 30 va each (0.25 amp at

 

120 vac, 0.13 amp at 230 vac). AHMS IFC-AUX contact must

 

have minimum pilot duty rating of 325 va each (2.7 amps at

 

120 vac, 1.4 amps at 230 vac).

5.

Replacement of factory wires must be with type 105 C wire or

 

its equivalent.

6.

Field-supplied liquid line solenoid valves installed at the evapo-

 

rator are required on all units.

7.

Control has 25 va of power available for ®eld-installed

 

accessories.

AHMS Ð Air Handler Motor Starter

AUX Ð Auxiliary

CÐ Compressor Contactor

FU Ð Fuse

GND

Ð Equipment Ground

IFC

Ð

Indoor Fan Control

kcmil

Ð

Thousand Circular Mils

LLS

Ð

Liquid Line Solenoid

NEC

Ð National Electrical Code

 

 

(U.S.A. Standard)

SDR

Ð Solenoid Drop Relay

TB

Ð Terminal Block

TBX

Ð Terminal Block for Variable

TM

Air Volume Units

Ð Timer Motor

TR

Ð Timer Relay

TRAN Ð Transformer

UÐ Unloader Solenoid

Factory Wiring Field Wiring

Fig. 26 Ð Field Wiring, Single ModuPanel™ Control, Unit 38AH094