Carrier 38AH044-084 specifications Ð Double Suction Riser Construction

Models: 38AH044-084

1 56
Download 56 pages 61.81 Kb
Page 15
Image 15
Fig. 13 Ð Double Suction Riser Construction

*Field-Supplied.

Fig. 12 Ð Required Location of Solenoid Valves and Recommended Filter Drier and

Sight Glass Locations for 38AH044-084 Optional Single-Circuit Units

LEGEND

AÐ Pipe A, Suction Riser, without Trap

BÐ Pipe B, Suction Riser with Trap

CÐ Suction Line to Condensing Unit

DÐ Pipe D, Suction Riser Short Lift RED. Ð Reducer

STR Ð Street

NOTES:

1.Short riser, pipe D, is used when routing suction line to condens- ing unit connection. See table at right.

2.See Tables 6A-9B for values of A, B, and C.

 

 

 

 

PIPE D DIAMETER

 

UNIT

 

 

Dual Circuit*

 

 

Single Circuit*

38AH

A

 

 

B

 

 

 

 

 

in.

 

mm

in.

 

mm

in.

mm

044

15¤8

 

41

15¤8

 

41

21¤8

54

054

15¤8

 

41

15¤8

 

41

21¤8

54

064

15¤8

 

41

21¤8

 

54

21¤8

54

074

21¤8

 

54

21¤8

 

54

21¤8

54

084

21¤8

 

54

21¤8

 

54

25¤8²

67²

094, 104

21¤8

 

54

21¤8

 

54

Ð

Ð

124, 134

25¤8

 

67

25¤8

 

67

Ð

Ð

*Maximum length of riser is 3 ft (914 mm).

²Double suction riser required if accessory unloader is ®eld installed.

Fig. 13 Ð Double Suction Riser Construction

15

Page 15
Image 15
Carrier 38AH044-084 specifications Ð Double Suction Riser Construction