Table 8A Ð Refrigerant Piping Requirements for
Optional Single-Circuit Units and 38AH124,134
Modular Units (Dual-Circuit) Ð 60 Hz
|
|
|
|
| TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE Ð FT (M) |
|
| |||||||||
UNIT |
|
|
|
| ||||||||||||
38AH | ||||||||||||||||
| L |
| S | L |
| S | L |
| S | L |
| S | L | S | L | S |
044 | 7¤8 |
| 21¤8 | 7¤8 |
| 21¤8 | 11¤8 |
| 21¤8 | 11¤8 |
| 25¤8* | 13¤8 | 25¤8* | 13¤8 | 31¤8* |
054 | 7¤8 |
| 21¤8 | 11¤8 |
| 25¤8 | 11¤8 |
| 25¤8 | 11¤8 |
| 25¤8 | 13¤8 | 31¤8* | 13¤8 | 31¤8* |
064; |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Modules 124A, | 11¤8 |
| 21¤8 | 11¤8 |
| 25¤8² | 1 1¤8 |
| 25¤8² | 1 3¤8 |
| 31¤8* | 13¤8 | 31¤8* | 13¤8 | 31¤8* |
124B,134A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
074; | 11¤8 |
| 21¤8 | 11¤8 |
| 25¤8² | 1 3¤8 |
| 31¤8² | 1 3¤8 |
| 31¤8² | 1 3¤8 | 31¤8² | 1 5¤8 | 35¤8* |
Module 134B |
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
084 | 11¤8 |
| 25¤8² | 1 1¤8 |
| 25¤8² | 1 3¤8 |
| 31¤8² | 1 3¤8 |
| 31¤8² | 1 5¤8 | 35¤8² | 1 5¤8 | 35¤8* |
LEGEND
CV Ð Constant Volume
LÐ Liquid Line
S Ð Suction Line
VAV Ð Variable Air Volume
*Double suction riser required on all units con®gurations if condens- ing unit is elevated above evaporator.
²Double suction riser required on units with factory installed VAV op- tion or CV units with additional ®eld installed unloader on circuit A1 (lead) compressor if condensing unit is elevated above evaporator.
NOTES:
1.Addition of
2.Piping sizes are based on unit operation above 40 F (4.4 C) satu- rated suction temperature (SST). When operating below 40 F (4.4 C), refer to Carrier System Design Manual,
3.Pipe sizes are based on the total linear length shown for each column, plus a 50% allowance for ®ttings.
4.Suction and liquid line sizing is based on pressure drop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop
design criteria may allow selection of smaller pipe sizes, but at a penalty of decreased system capacity and ef®ciency.
5.Double suction risers may be required if condensing unit is elevated above the evaporator. See footnotes and double suction riser table below.
6.Refer to Carrier System Design Manual,
7.All pipe sizes are OD inches. Equivalent sizes in millimeters follow:
in. | mm |
7¤8 | 22.2 |
11¤8 | 28.6 |
13¤8 | 34.9 |
15¤8 | 41.3 |
21¤8 | 54.0 |
25¤8 | 66.7 |
31¤8 | 79.4 |
35¤8 | 92.1 |
Table 8B Ð Refrigerant Piping Requirements for Double Suction Risers,
Modular Units
|
|
|
|
|
| TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE Ð FT |
|
|
|
|
| ||||||||||||||
UNIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
38AH |
|
|
|
|
|
|
|
|
|
| |||||||||||||||
| A |
| B |
| C | A |
| B |
| C | A |
| B |
| C | A |
| B |
| C | A |
| B |
| C |
044 | Ð |
| Ð |
| Ð | Ð | Ð | Ð |
| 1 | 5¤8 |
| 21¤8 |
| 25¤8 | 15¤8 |
| 21¤8 |
| 25¤8 | 15¤8 |
| 25¤8 |
| 31¤8 |
054 | Ð |
| Ð |
| Ð | Ð | Ð | Ð |
| Ð | Ð |
| Ð |
| 1 | 5¤8 |
| 25¤8 |
| 31¤8 | 15¤8 |
| 25¤8 |
| 31¤8 |
064 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Modules 124A, | 15¤8 |
| 21¤8 |
| 25¤8 | 15¤8 |
| 21¤8 |
| 25¤8 | 15¤8 |
| 25¤8 |
| 31¤8 | 15¤8 |
| 25¤8 |
| 31¤8 | 15¤8 |
| 25¤8 |
| 31¤8 |
124B,134A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
074; | 15¤8 |
| 21¤8 |
| 25¤8 | 15¤8 |
| 25¤8 |
| 31¤8 | 15¤8 |
| 25¤8 |
| 31¤8 | 15¤8 |
| 25¤8 |
| 31¤8 | 21¤8 |
| 31¤8 |
| 35¤8 |
Module 134B |
|
|
|
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
084 | 15¤8 |
| 21¤8 |
| 25¤8 | 15¤8 |
| 25¤8 |
| 31¤8 | 15¤8 |
| 25¤8 |
| 31¤8 | 21¤8 |
| 31¤8 |
| 35¤8 | 21¤8 |
| 31¤8 |
| 35¤8 |
LEGEND
ÐÐ Not Required
Pipe A Ð Suction Riser Without Trap
Pipe B Ð Suction Riser With Trap
Pipe C Ð Suction Line to Condensing Unit
NOTES:
1.See Refrigerant Piping Requirements table at top of page to de- termine need for double suction risers.
2.Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for ®ttings.
3.Suction and liquid line sizing is based on pressure drop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher design pressure drop criteria may allow selection of smaller pipe sizes but at a pen- alty of decreased system capacity and ef®ciency.
4.Refer to Carrier System Design Manual or to
5.All pipe sizes are OD inches. See Table 8A notes for metric equivalents.
6.Refer to Fig. 13 for double suction riser construction.
18