Optional Single-Circuit Units and 38AH124,134

Table 8A Ð Refrigerant Piping Requirements for 38AH044-084

Optional Single-Circuit Units and 38AH124,134

Modular Units (Dual-Circuit) Ð 60 Hz

 

 

 

 

 

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE Ð FT (M)

 

 

UNIT

 

15-20

 

20-50

 

50-75

 

75-100

100-150

150-200

38AH

(4.6-6.1)

(6.1-15.2)

(15.2-22.9)

(22.9-30.5)

(30.5-45.7)

(45.7-61.0)

 

L

 

S

L

 

S

L

 

S

L

 

S

L

S

L

S

044

7¤8

 

21¤8

7¤8

 

21¤8

11¤8

 

21¤8

11¤8

 

25¤8*

13¤8

25¤8*

13¤8

31¤8*

054

7¤8

 

21¤8

11¤8

 

25¤8

11¤8

 

25¤8

11¤8

 

25¤8

13¤8

31¤8*

13¤8

31¤8*

064;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modules 124A,

11¤8

 

21¤8

11¤8

 

25¤8²

1 1¤8

 

25¤8²

1 3¤8

 

31¤8*

13¤8

31¤8*

13¤8

31¤8*

124B,134A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

074;

11¤8

 

21¤8

11¤8

 

25¤8²

1 3¤8

 

31¤8²

1 3¤8

 

31¤8²

1 3¤8

31¤8²

1 5¤8

35¤8*

Module 134B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

084

11¤8

 

25¤8²

1 1¤8

 

25¤8²

1 3¤8

 

31¤8²

1 3¤8

 

31¤8²

1 5¤8

35¤8²

1 5¤8

35¤8*

LEGEND

CV Ð Constant Volume

LÐ Liquid Line

S Ð Suction Line

VAV Ð Variable Air Volume

*Double suction riser required on all units con®gurations if condens- ing unit is elevated above evaporator.

²Double suction riser required on units with factory installed VAV op- tion or CV units with additional ®eld installed unloader on circuit A1 (lead) compressor if condensing unit is elevated above evaporator.

NOTES:

1.Addition of ®eld-installed unloaders on A2 (lag) compressor is not recommended.

2.Piping sizes are based on unit operation above 40 F (4.4 C) satu- rated suction temperature (SST). When operating below 40 F (4.4 C), refer to Carrier System Design Manual, E20-II piping design program, or ASHRAE Handbook to select proper line sizes.

3.Pipe sizes are based on the total linear length shown for each column, plus a 50% allowance for ®ttings.

4.Suction and liquid line sizing is based on pressure drop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop

design criteria may allow selection of smaller pipe sizes, but at a penalty of decreased system capacity and ef®ciency.

5.Double suction risers may be required if condensing unit is elevated above the evaporator. See footnotes and double suction riser table below.

6.Refer to Carrier System Design Manual, E20-II design program, or ASHRAE Handbook for further information on selecting pipe sizes for split systems.

7.All pipe sizes are OD inches. Equivalent sizes in millimeters follow:

in.

mm

7¤8

22.2

11¤8

28.6

13¤8

34.9

15¤8

41.3

21¤8

54.0

25¤8

66.7

31¤8

79.4

35¤8

92.1

Table 8B Ð Refrigerant Piping Requirements for Double Suction Risers,

38AH044-084 Optional Single-Circuit Units and 38AH124,134

Modular Units (Dual-Circuit) Ð 60 Hz

 

 

 

 

 

 

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE Ð FT

 

 

 

 

 

UNIT

 

15-50

 

 

 

 

50-75

 

 

 

75-100

 

 

 

100-150

 

 

 

150-200

 

 

38AH

 

(4.6-15.2)

 

 

(15.2-22.9)

 

 

(22.9-30.5)

 

 

(30.5-45.7)

 

 

(45.7-61.0)

 

 

A

 

B

 

C

A

 

B

 

C

A

 

B

 

C

A

 

B

 

C

A

 

B

 

C

044

Ð

 

Ð

 

Ð

Ð

Ð

Ð

 

1

5¤8

 

21¤8

 

25¤8

15¤8

 

21¤8

 

25¤8

15¤8

 

25¤8

 

31¤8

054

Ð

 

Ð

 

Ð

Ð

Ð

Ð

 

Ð

Ð

 

Ð

 

1

5¤8

 

25¤8

 

31¤8

15¤8

 

25¤8

 

31¤8

064

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modules 124A,

15¤8

 

21¤8

 

25¤8

15¤8

 

21¤8

 

25¤8

15¤8

 

25¤8

 

31¤8

15¤8

 

25¤8

 

31¤8

15¤8

 

25¤8

 

31¤8

124B,134A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

074;

15¤8

 

21¤8

 

25¤8

15¤8

 

25¤8

 

31¤8

15¤8

 

25¤8

 

31¤8

15¤8

 

25¤8

 

31¤8

21¤8

 

31¤8

 

35¤8

Module 134B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

084

15¤8

 

21¤8

 

25¤8

15¤8

 

25¤8

 

31¤8

15¤8

 

25¤8

 

31¤8

21¤8

 

31¤8

 

35¤8

21¤8

 

31¤8

 

35¤8

LEGEND

ÐÐ Not Required

Pipe A Ð Suction Riser Without Trap

Pipe B Ð Suction Riser With Trap

Pipe C Ð Suction Line to Condensing Unit

NOTES:

1.See Refrigerant Piping Requirements table at top of page to de- termine need for double suction risers.

2.Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for ®ttings.

3.Suction and liquid line sizing is based on pressure drop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher design pressure drop criteria may allow selection of smaller pipe sizes but at a pen- alty of decreased system capacity and ef®ciency.

4.Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems.

5.All pipe sizes are OD inches. See Table 8A notes for metric equivalents.