Carrier A Ð One 2-StageThermostat Capacity, Control for 38AH044-084 Dual-CircuitUnits

Models: 38AH044-084

1 56
Download 56 pages 61.81 Kb
Page 48
Image 48

Table 19A Ð One 2-Stage Thermostat Capacity

Control for 38AH044-084 Dual-Circuit Units

 

QUANTITY OF LOADED

SYSTEM

UNIT

COMPRESSOR CYLINDERS

CAPACITY

38AH

Circuit

Circuit

Total

(%)

 

A

B

 

 

 

 

4

4

8

100

044

2

4

6

75

4

0

4

50

 

 

2

0

2

25

 

4

6

10

100

054

2

6

8

79

2

4

6*

59

 

4

0

4

42

 

2

0

2

21

 

6

6

12

100

 

4

6

10

84

064

2

6

8*

68

6

0

6

48

 

 

4

0

4

32

 

2

0

2*

16

 

6

6

12

100

 

4

6

10

86

074

2

6

8*

72

6

0

6

43

 

 

4

0

4

29

 

2

0

2*

15

 

6

6

12

100

 

4

6

10

83

084

2

6

8*

66

6

0

6

50

 

 

4

0

4

33

 

2

0

2*

17

*Requires units with VAV (variable air volume) factory-supplied option.

NOTE: Units have 2 independent refrigeration circuits. Circuit A is lead circuit.

Table 19B Ð One 2-Stage Thermostat Capacity Control for 38AH044-084 Optional Single-Circuit Units

UNIT

QUANTITY OF

SYSTEM

CAPACITY

38AH

LOADED CYLINDERS

(%)

 

 

 

8

100

044

6

75

4

50

 

 

2

25

 

10

100

 

8

81

054

6

60

6

56

 

 

4

37

 

2*

19*

 

12

100

 

10

82

064

8

64

6

56

 

 

4

36

 

18

 

12

100

 

10

81

074

8

62

6

57

 

 

4

38

 

19

 

12

100

 

10

83

084

8

66

6

50

 

 

4

33

 

17

*Requires accessory unloader on lead 06E-265 compressor (A1). ²Requires VAV (variable air volume) factory-installed option or ac-

cessory unloader.

Table 20 Ð One 2-Stage Thermostat Capacity

Control for 38AH094-134 Units

UNIT

QUANTITY OF LOADED

SYSTEM

COMPRESSOR CYLINDERS

CAPACITY

38AH

Ckt A

Ckt B

Total

(%)

 

 

10

6

16

100

 

10

4

14

85

 

10

2

12

70*

094

10

0

10

55

8

0

8

44

 

6

0

6

33

 

4

0

4

22

 

10

12

22

100

 

8

12

20

91

 

8

10

18

82

 

10

6

16

73

104

6

6

12

55

6

4

10

45

 

 

0

6

6

27

 

4

0

4

18

 

0

4

4

18

 

0

2

 

12

12

24

100

 

10

12

22

92

 

10

10

20

83

 

8*

10

18

75*

124

6

10

16

67

6

8*

14

58*

 

6

6

12

50

 

4

6

10

42

 

6

0

6

25

 

4

0

4

17

 

2*

0

2

8*

 

12

12

24

100

 

10

12

22

92

 

10

10

20

83

 

8*

10

18

75*

134

6

10

16

67

6

8*

14

58*

 

6

6

12

50

 

4

6

10

42

 

6

0

6

25

 

4

0

4

17

 

2*

0

2

8*

*Requires VAV (variable air volume) unit or accessory unloader(s) field installed on circuit lead compressor. Lead compressor is identi®ed in Table 16, page 40.

²Requires ®eld-installed accessory unloader on circuit lead compres- sor. Lead compressor is identi®ed in Table 16, page 40.

NOTES:

1.Temperatures calculated with the minimum number of fans oper- ating per circuit.

2.See Table 16, page 40, for information on lead and lag circuits.

CONTROL SET POINT Ð Control set point (cylinder load point) is adjustable from 0 to 85 psig (0 to 586 kPag). To adjust the set point, turn the control set point adjust- ment nut clockwise to bottom stop. (See Fig. 46.) In this position, load-up set point is 85 psig (586 kPag). Turn adjustment counterclockwise to desired control set point. Every full turn clockwise decreases the load-up set point by 7.5 psig (52 kPag).

PRESSURE DIFFERENTIAL Ð Pressure differential (difference between cylinder load and unload points) is adjustable from 6 to 22 psig (41 to 152 kPag). To adjust, turn pressure differential adjustment screw counterclock- wise to back stop position. The differential pressure is now adjusted to 6 psig (41 kPag). Turn the adjustment screw clock- wise to adjust the differential pressure. Every full clockwise turn increases the differential by 1.5 psig (10 kPag).

48

Page 48
Image 48
Carrier A Ð One 2-StageThermostat Capacity, Control for 38AH044-084 Dual-CircuitUnits, Control for 38AH094-134Units