Table 12 Ð Electrical Data Ð 50/60 Hz (Units 38AH124, 134)
UNIT | VOLTAGE | COMPRESSOR | NAMEPLATE | SUPPLY |
|
|
|
| COMPRESSOR² |
| ||||
38AH | A1/A2 | VOLTAGE* | MCA | MOCP | ICF | A1 | A2 |
| ||||||
DESIGNATION |
| |||||||||||||
MODULE | MODEL NO. |
|
|
|
|
|
|
|
|
|
|
| ||
|
| Min | Max |
|
|
| RLA |
| LRA | RLA |
| LRA | ||
|
|
|
|
|
|
|
|
| ||||||
| 500 |
| 187 | 254 | 249.3 | 350 | 617.5 | 106.4 |
| 506 | 89.7 |
| 446 | |
124A | 600 |
| 414 | 508 | 115.5 | 150 | 307.6 | 46.8 |
| 253 | 43.6 |
| 223 | |
100 | 06E8275/ | 518 | 632 | 100.6 | 125 | 226.1 | 40.4 |
| 176 | 36.5 |
| 164 | ||
124B |
|
| ||||||||||||
200 | 265 | 342 | 418 | 126.9 | 175 | 341.1 | 52.6 |
| 280 | 45.5 |
| 247 | ||
134A |
|
| ||||||||||||
| 900 |
| 342 | 440 | 115.7 | 150 | 335.6 | 46.8 |
| 280 | 43.6 |
| 223 | |
| 300 (PW) |
| 325 | 367 | 129.8 | 175 | 230.5 | 53.8 |
| 168 | 44.9 |
| 148 | |
| 500 |
| 187 | 254 | 330.5 | 450 | 829.0 | 147.4 |
| 690 | 106.4 |
| 506 | |
| 600 |
| 414 | 508 | 148.6 | 200 | 408.2 | 65.4 |
| 345 | 46.8 |
| 253 | |
134B | 100 | 06E8299/ | 518 | 632 | 132.2 | 175 | 336.8 | 57.1 |
| 276 | 40.4 |
| 176 | |
200 | 275 | 342 | 418 | 174.5 | 250 | 458.0 | 78.8 |
| 382 | 52.6 |
| 280 | ||
|
|
| ||||||||||||
| 900 |
| 342 | 440 | 149.0 | 200 | 403.8 | 65.4 |
| 345 | 46.8 |
| 280 | |
| 300 (PW) |
| 325 | 367 | 170.8 | 250 | 300.4 | 79.5 |
| 229 | 53.8 |
| 168 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LEGEND |
FLA | Ð Full Load Amps |
ICF | Ð Maximum Instantaneous Current Flow During Starting. |
| (The point in the starting sequence where the sum of |
| the LRA for the starting compressors, plus the total RLA |
| for all running compressors, plus the FLA for all running |
| fan motors is maximum.) |
kcmil | Ð Thousand Circular Mils |
LRA | Ð Locked Rotor Amps |
MCA | Ð Minimum Circuit Amps (used for sizing; complies with |
| National Electrical Code [NEC] [U.S.A. Standard], |
| section |
MOCP Ð Maximum Overcurrent Protection (used for sizing | |
| disconnect; complies with NEC [U.S.A. Standard], |
| section 440- 22). |
PW | Ð Part Wind |
RLA | Ð Rated Load Amps |
*Units are suitable for use on electrical systems where voltage sup- plied to unit terminals is within listed minimum to maximum limits.
²All compressors are
NOTES:
1.Maximum allowable phase imbalance: voltage - 2%; amps - 10%.
2.Maximum incoming wire size for terminal block is 500 kcmil.
Table 13 Ð Control Circuit Electrical Data Ð 50/60 Hz
UNIT | UNIT POWER | CONTROL POWER |
| AMPS | ||
DESIGNATION | Min |
| Max | |||
|
| |||||
−500 | 103 |
| 127 | 4.1 | ||
−600 | 103 |
| 127 | 4.1 | ||
−100 | 103 |
| 127 | 4.1 | ||
−200 | 207 |
| 253 | 2.0 | ||
−800 | 207 |
| 253 | 2.0 | ||
−900 | 207 |
| 253 | 2.0 | ||
−300 | 180 |
| 220 | 2.4 |
NOTE: Units 38AH124 and 134 have 2 control boxes per unit, one in each module.