Mitsubishi Electronics PDFY-P06NMU-E, PDFY-P30NMU-E, PDFY-P08NMU-E Linear expansion valve

Models: PDFY-P06NMU-E PDFY-P36NMU-E PDFY-P24NMU-E PDFY-P08NMU-E PDFY-P48NMU-E PDFY-P15NMU-E PDFY-P27NMU-E PDFY-P18NMU-E PDFY-P12NMU-E PDFY-P30NMU-E

1 25
Download 25 pages 36.66 Kb
Page 15
Image 15

<Thermistor Characteristic graph>

< Thermistor for lower temperature >

Thermistor for

Room temparature thermistor(TH21)

50

lower temperature Liquid pipe thermistor(TH22)

Gas pipe temparature thermistor(TH23) Drain sensor(DS)

Thermistor R0=15kΩ ± 3%

Fixed number of B=3480kΩ ± 2%

Rt=15exp { 3480(

1

 

 

 

1

) }

273+t

273

 

 

0˚C 32˚F 15k

10˚C 50˚F 9.6k

20˚C 68˚F 6.3k

25˚C 77˚F 5.2k

30˚C 86˚F 4.3k

40˚C 104˚F 3.0k

Resistance (k )

40

30

20

10

0

-20 -10 0 10 20 30 40 50 (˚C) -4 14 32 50 68 86 104 122 [˚F]

Temperature

Linear expansion valve

1Operation summary of the linear expansion valve.

Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.

Valve position can be changed in proportion to the number of pulse signal.

<Connection between the indoor controller board and the linear expasion valve>

Linear expansion valve

4 Blue

M 6 Brown

Yellow

52

1 3

White Red Orange

Controller board

 

 

 

DC12V

 

Brown

6

 

 

Red

5

Drive circuit

 

 

 

ø4

Blue

4

ø4

ø3

Orange

3

ø3

ø2

Yellow

2

ø2

ø1

White

1

ø1

 

Connector(CN60)

 

 

14

Page 15
Image 15
Mitsubishi Electronics PDFY-P06NMU-E service manual Linear expansion valve, Operation summary of the linear expansion valve