Monessen Hearth BDV500 Minimum Height, Roof Pitch Feet Meters, Cathedral Ceiling Installation

Models: BDV400 BDV500 BDV300 BDV600

1 52
Download 52 pages 34.58 Kb
Page 25
Image 25
TERMINATION HEIGHT TABLE
Use this table to determine the minimum height above the roof.
12"
X
Cone flashing
H
Storm collar
Termination

VENT INSTALLATION

3.Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof). The 91/2"x91/2" (241mm x 241mm) hole must be measured on the horizontal. Actual length may be larger depending on the pitch of the roof. There must be a 1" minimum clearance from the vent pipe to combustible materials. (Insulation should be considered a combustible material).

4.Connect a section of pipe and extend up through the hole.

NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three (3) feet. Use wall straps for this purpose. See Figure 28, page 23. Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.

5.Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing. There must be a 1" clearance from the vent pipe to combustible materials.

6.Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements.

NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.

NOTE: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock

the enclosure with standard construction material. Make sure to meet the minimum allowable clearances to combustibles. Do not fill any of the required clearance spaces with insulation.

CATHEDRAL CEILING INSTALLATION

1. Remove shingles or other roof covering as necessary to cut the rect- angular hole for the support box. Mark the outline of the cathedral ceiling support box on the roof sheathing using the locating hole as a center point.

2.Cut the hole 1/8" larger than the support box outline. See Figure 32. Figure 35 - Minimum Chimney Clearance

3.Lower the support box through the hole in the roof until the bottom of the box extends at least 2" below the ceiling. See

Figure 32. Align the support box vertically and horizontally using a level. Temporarily tack the support box in place through the inside walls and into the roof sheeting.

4. Using tin snips, cut the support box from the

 

Minimum Height

 

top corners down to the roof line and fold

 

 

 

 

 

 

the resulting flaps over the roof sheeting.

Roof Pitch

Feet

Meters

 

See Figure 33. Apply a bead of non-hard-

 

 

 

 

Flat to 7/12

1

0.3

 

ening, mastic around the top edges of the

 

Over 7/12 to 8/12

1.5

0.46

 

support box to make a seal between the

 

box and the roof. Nail in place with roofing

Over 8/12 to 9/12

2

0.61

 

nails. Remove any combustible material that

Over 9/12 to 10/12

2.5

0.76

 

might be inside the support box.

Over 10/12 to 11/12

3.25

0.99

 

5. Complete the cathedral ceiling installation by

 

Over 11/12 to 12/12

4

1.22

 

following the same procedures outlines in

 

Over 12/12 to 14/12

5

1.52

 

steps 2 through 6 for Flat Ceiling Installation,

 

page 24 and above.

 

 

 

 

 

 

 

 

54D0700

25

Page 25
Image 25
Monessen Hearth BDV500, BDV600, BDV300, BDV400 Minimum Height, Roof Pitch Feet Meters, Cathedral Ceiling Installation