FIREPLACE FRAMING
FIREBOX FRAMING
Firebox framing can be built before or after the appliance is set in place. Construct firebox framing following Figure 2 and the chart below for your specific installation requirements. See Figure 3 on Page 8 for firebox dimensions. The framing headers may rest on the top of the firebox standoffs. Do not bring headers below top of standoffs.
The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height. When the firebox is installed directly on carpeting, tile, or other combustible material, other than wood flooring, the firebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure.
WARNING
Do not fill spaces around firebox with insulation or other materials. This could cause a fire.
D
F
G
C
| 300 | 400 | 500 | 600 |
A | 331/2" | 371/2" | 411/2" | 471/2" |
B | 371/4" | 407/8" | 407/8" | 407/8" |
C | 281/4" | 291/4" | 331/4" | 391/4" |
D | 141/8" | 145/8" | 165/8" | 195/8" |
E | 5511/16" | 607/8" | 647/8" | 707/8" |
F | 2713/16" | 307/16" | 327/16" | 357/16" |
G | 133/4" | 153/4" | 153/4" | 153/4" |
H | 393/8" | 431/16" | 457/8" | 501/8" |
A
E
Corner Installation
C
A
Inside Chase Installation
G
1/ " 5/ "
B
A
Stud Location
C
A
Recessed Installation
Figure 2 - Framing Dimensions
G
1/2" or 5/8
54D0700 | 7 |