EYF Series Unvented Gas Log Set | ELECTRICAL WIRING - MILLIVOLT |
Connecting optional Remote Re- ceiver
Follow instructions supplied with the remote
1.Connect the wires to the two .25" male connectors located on the left side of the valve when facing the unit. Page 19, Figure 16. Do not let wire touch grate or burner.
2.Stick velcro pads with
3.Attach remote receiver with velcro pads. Control switch must face forward.
NOTE: Heat reduces battery life. You can protect the receiver and extend battery life by mounting the receiver in a wall or other location outside the fireplace.
CHECKING SYSTEM OPERATION
The millivolt system and individual components may be checked with a millivolt meter having a
A.Complete Millivolt System Check
(“A” Reading - Thermostat contacts CLOSED - Control knob “ON” - Main burner should turn ON)
1.If reading is more than 175 millivolts and the au- tomatic valve still does not come on, replace the control.
2.If the closed circuit reading (“A” reading) is less than 175 millivolts, determine cause for low read- ing, proceed to Section B.
B.Thermopile Output Reading Check
(“B” Reading - thermostat contacts OPEN - Main burn- er OFF
1.Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot voltage, 500 millivolts minimum. If the minimum millivolt reading is not obtainable, replace pilot.
|
|
| Connect | Switch or | Meter |
Check |
|
| Meter Leads | Thermostat | Reading |
Test | To Test |
| To Terminals | Contacts | Should Be |
A | Complete |
| 2 & 3 | Closed | Minimum 175 |
| System |
|
|
|
|
B | Thermopile |
| 1 & 2 | Open | Minimum 500 |
| Output |
|
|
|
|
|
|
| Velcro |
|
|
| Remote |
| Pads |
|
|
|
|
|
|
| |
| Receiver |
|
|
|
|
| SKYTECH |
|
|
|
|
| OFF | REMOTE |
|
|
|
|
| ON |
|
|
Figure 17 -
Install Remote Receiver
HI OFF
FP2540
14 | 65D1009 |