CLEARANCE and HEIGHT REQUIREMENTS

EYF Series Unvented Gas Log Set

INSTALLATION

CLEARANCE and HEIGHT REQUIREMENTS

WARNING

The dimensions shown in Figures 4 through 10 and defined in the fireplace manufacturer's instructions are minimum clearances to maintain when installing this heater. Left and right clearances are determined when facing the front of the heater.

When heater is installed into a ventless firebox, minimum clearances, as specified by the ventless firebox manufacturer, must be met.

Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire hazard.

Sidewall and ceiling clearances: The sides of the fire- place opening must be at least 16" from any combustible wall. The ceiling must be at least 42" from the top of the fireplace opening.

42"

16"

FP1996

Figure 4 -

Sidewall and Ceiling Clearances

Heat resistant material (minimum requirements) with no wooden mantel or other combustible projection:

To install the gas logs into a fireplace with no wooden mantel, shelf or other combustible projection above the fireplace opening, measure the heat resistant material height, per Figure 5, then see TABLE A.

Heat resistant materials such as slate and marble must be

at least 1/2" thick. Sheet metal should not be installed onto combustible material.

IMPORTANT: If you cannot meet these minimum clear- ances you must operate the heater with chimney flue damper open. See Installing Vented Applications found on page 16.

Heat

Resistant

Material

Measure This

Distance

Heater in Fireplace

or Firebox

FP2533

Figure 5 -

Mantel Clearance without Hood

Table A -

Heat Resistant Material Requirements with No Mantel or Combustible Projection

Heat Resistant Material

EYF24/18 Requirements

Measurement

for Safe Installation

20" or more

Hood not required

8" to less than 20"

Extend heat resistant material

 

to 20" or install hood. Figure 6

Less than 8"

Extend heat resistant material

 

to at least 8" and install hood.

 

Figure 6. OR, extend heat

 

resistant material to a height

 

of at least 20".