MGate EIP3000 Series User’s Manual

Hardware: EIP3170, EIP3170I

Jumpers

SW 1

The DIP switches are located beneath the DIP switch panel on the side of the unit.

To add a 120 Ω termination resistor, set switch 3 to ON; set switch 3 to OFF (the default setting) to disable the termination resistor.

To set the pull high/low resistors to 150 KΩ, set switches 1 and 2 to OFF. This is the default setting.

To set the pull high/low resistors to 1 KΩ, set switches 1 and 2 to ON.

Switch 4 on the port’s assigned DIP switch is reserved.

ATTENTION

Do not use the 1 KΩ pull high/low setting on the MGate EIP3000 when using the RS-232 interface. Doing so will degrade the RS-232 signals and reduce the effective communication distance.

3-4

Page 14
Image 14
Moxa Technologies EIP3000 DF1 user manual Jumpers