Multiquip DCA-180SSV- Generator OUTPUTS/ Gauge Reading, Maximum Amps, Change-Over Switch

Models: DCA-180SSV

1 84
Download 84 pages 39.22 Kb
Page 29
Image 29

DCA-180SSV— GENERATOR OUTPUTS/ GAUGE READING

Maximum Amps

Table 10 shows the maximum amps the generator can pro- vide. DO NOT exceed the maximum amps as listed.

Table 10. Generator Maximum Amps

Model

DCA220SSVU

 

 

Rated Voltage

Maximum Amps

 

 

Single Phase

400 amps (4 wire)

120 Volt

 

 

 

Single Phase

200 amps (4 wire)

240 Volt

 

 

 

Three Phase

433 amps

240 Volt

 

 

 

Three Phase

216 amps

480 Volt

 

 

 

Figure 16. AC Voltmeter

Figure 17. AC Voltmeter Gauge

Change-Over Switch

(Volt reading on W-U Lug)

How to Read the Output Terminal Gauge.

The AC ammeter and AC voltmeter change-over switches on the control panel DO NOT effect the generator output. They are provided to help observe how much power is being supplied, produced at the UVWO terminals lugs.

When the voltage change-over board is jumpered for 3Ø, 240V operation (See Figures 16 and17), place the AC Volt- meter Change-Over Switch (See Figures 18 and 19) to the W-U position and the AC Ammeter Change-Over Switch (Figure 18) to the U or W position to read the output on the selected leg.

Figure 18. AC Ammeter

Change-Over Switch

NOTE

Figure 19. AC Ammeter (Amp reading on U lug)

The ammeter gauge will only show a reading when the Output Terminal Lugs are connected to a load and in use.

Figure 15. Voltage Change-Over Board 240V Configuration

DCA-180SSV— OPERATION AND PARTS MANUAL — REV. #1 (04/14/10) — PAGE 29

Page 29
Image 29
Multiquip DCA-180SSV- Generator OUTPUTS/ Gauge Reading, Maximum Amps, How to Read the Output Terminal Gauge