DCA-180SSV — GENERATOR OUTPUTS

Generator OutputVoltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by apply- ing jumpers (6) to the voltage change-over board (Figure 14). To obtain some of the voltages as listed in Table 6 (see below) will require a fine adjustment using the voltage regu- lator (VR) control knob located on the control panel.

Voltage Change-Over Board

The voltage change-over board (Figure 14) is located on the control box, behind the generator control panel. This board has been provided for ease of voltage selection.

Generator Amperage

Tables 8 and 9 describe the generator’s current output capa- bility for both 1Ø-phase and 3Ø phase applications.

Table 8. Generator Ampere Ratings 1

kW

120V

240V

 

 

 

18

150

75

 

 

 

38

316

158

 

 

 

58

483

267

 

 

 

78

650

236

 

 

 

98

817

492

 

 

 

118

983

319

 

 

 

138

1,150

575

 

 

 

158 (Max)

1,317

658

 

 

 

Figure 14. Voltage Change-Over Board

CAUTION - CHANGINGVOLTAGES

NEVER attempt to place jumper plates on the voltage change-over board while the generator is in operation. There exist the possibility of electrocution, electrical shock or burn, which can cause severe bodily harm or even death!

Table 7. Voltages Available

Three Phase

208V

220V

240V

416V

440V

480V

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

120V

127V

139V

240V

254V

277V

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 9. Generator Ampere Ratings 3

KVA

240V

480V

 

 

 

20

48

24

 

 

 

40

96

48

 

 

 

60

144

72

 

 

 

80

192

96

 

 

 

100

241

120

 

 

 

120

289

144

 

 

 

140

337

168

 

 

 

160

384

192

 

 

 

180 (Max)

433

216

 

 

 

PAGE 28 — DCA-180SSV— OPERATION AND PARTS MANUAL — REV. #1 (04/14/10)

Page 28
Image 28
Multiquip operation manual DCA-180SSV Generator Outputs