Multiquip operation manual DCA-25SSIU2 50 HZ- GENERATOR CONTROL PANEL, Generator Control Panel

Models: DCA-25SSIU2

1 82
Download 82 pages 62.92 Kb
Page 20
Image 20
DCA-25SSIU2 (50 HZ)— GENERATOR CONTROL PANEL

DCA-25SSIU2 (50 HZ)— GENERATOR CONTROL PANEL

Figure 6. Generator Control Panel

The definitions below describe the controls and functions of the DCA-25SSIU2(50 HZ) Generator Control Panel (Figure 6).

1.Main Circuit Breaker – This three-pole, 60A main breaker is provided to protect the U,V, and W Output Terminal Lugs from overload.

2.Voltage Regulator Control – Allows ±15% manual adjustment of the generator’s output voltage

3.Frequency Meter – Indicates the output frequency in hertz (Hz). Normally 50 Hz.

4.AC Ammeter – Indicates the amount of current the load is drawing from the generator per leg selected by the ammeter phase-selector switch.

5.AC Voltmeter – Indicates the output voltage present at the U,V, and W Output Terminal Lugs.

6.Ammeter Change-Over Switch – This switch allows the AC ammeter to indicate the current flowing to the load connected to any phase of the output terminals, or to be switched off. This switch does not effect the generator output in any fashion, it is for current reading only.

7.Voltmeter Change-Over Switch – This switch allows the AC voltmeter to indicate phase to phase voltage between any two phases of the output terminals or to be switched off.

Located behind the generator control panel is the Generator Control Box. This box contains some of the necessary electronic components required to make the generator function.

The Control Box is equipped with the following major components:

Over-Current Relay

Voltage Rectifier (AVR)

Starter Relay

Current Transformer

Voltage Selector Switch

Remember the overcurrent

NOTErelay monitors the current flowing from the U,V, and W Output Terminal Lugs to the load.

In the event of a short circuit or over current condition, it will automatically trip the 60 amp main breaker.

To restore power to the Output Terminal Panel, press the reset button on the overcurrent relay and place the main circuit breaker in the closed position (ON).

PAGE 20 — DCA-25SSIU2 (50 HZ)— OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)

Page 20
Image 20
Multiquip operation manual DCA-25SSIU2 50 HZ- GENERATOR CONTROL PANEL, Generator Control Panel