Multiquip operation manual DCA-25SSIU2 50 HZ- GENERATOR START-UP PROCEDURE, Before Starting

Models: DCA-25SSIU2

1 82
Download 82 pages 62.92 Kb
Page 34
Image 34
DCA-25SSIU2 (50 HZ)— GENERATOR START-UP PROCEDURE

DCA-25SSIU2 (50 HZ)— GENERATOR START-UP PROCEDURE

Before Starting

CAUTION - LETHAL EXHAUST HAZARD

The engine's exhaust contains harmful emissions.

ALWAYS have adequate ventilation when operating.

Direct exhaust away from nearby personnel.

WARNING - STARTINGTHE GENERATOR

NEVER! manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.

1.Place the main, G.F.C.I., and aux. circuit breakers (Figure 39) in the OFF position prior to starting the engine.

Figure 39. Main, Aux. and GFCI

Circuit Breakers (OFF)

2.Connect the load to the receptacles or the Output Terminal Lugs as shown in Figure 13. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.

3.The output terminal lugs are protected by a plastic cover. Remove this cover to gain access to the terminals. Tighten terminal nuts securely to prevent load wires from slipping out.

4.Close all engine enclosure doors (Figure 40).

5.Place the voltage selector switch in the desired voltage position (Figure 41).

Figure 41. Voltage

Selector Switch

6.Preheat the engine glow plugs by turning the ignition key (Figure 42) to the “OPERATION” position.

Figure 42. Ignition Switch (Operation

Pre-Heat Position)

7.When the preheat lamp illuminates (Figure 43), turn the ignition key to the “START” position. Once the engine starts, release the ignition key and allow it to return to the “OPERATION” position (Figure 42).

Figure 43. Pre-Heat Indicator Lamp

8.Let the engine run for 3-5 minutes, listen and check for any abnormal sounds or smells. Check for fuel leaks, and noises that would associate with a loose cover or hardware. If any of the above mentioned conditions exists, shut-down the engine and correct the problem.

Figure 40. Engine Enclosure Doors

PAGE 34 — DCA-25SSIU2 (50 HZ)— OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)

Page 34
Image 34