Figure 44. Frequency Meter (Hz)

DCA-25SSIU2 (50 HZ)— GENERATOR START-UP PROCEDURE

9.The generator's frequency meter (Figure 44) displays the 50 cycle output frequency in HERTZ.

13.The engine oil pressure gauge (Figure 48) will indicate the oil pressure (kg/cm2) of the engine. Under normal operating conditions the oil pressure is between 28 ~71 psi (193 ~490 kPa).

Figure 44. Frequency Meter (Hz)

Figure 48. Oil Pressure Gauge

10.The generator's voltage meter (Figure 45) displays the 100VAC in VOLTS.If the voltage is not within the specified frequency tolerance,

14.The coolant temperature gauge (Figure 49) will indicate the coolant temperature. Under normal operating conditions the coolant temperature is between 165 and 203 degrees Fahrenheit (74 ~ 95 degrees Celsius).

Figure 45. AC Voltmeter

11.Use the voltage adjustment control knob (Figure 46) to increase or decrease the desired voltage.

Figure 46. Voltage Adjusted Control Knob

12.The ammeter (Figure 47) will indicate zero amps with no load applied. When a load is applied, this meter will indicate the amount of current that the load is drawing from the generator.

Figure 49. Coolant Temperature Gauge

15.The tachometer (Figure 50) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1500 RPM’s.

Figure 50. Engine Tachometer

Figure 47. Ammeter (No Load)

DCA-25SSIU2 (50 HZ)— OPERATION AND PARTS MANUAL — REV. #0 (03/11/05) — PAGE 35