LOAD APPLICATION

SINGLE PHASE LOAD

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is infl uenced by the effi ciency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

THREE PHASE LOAD

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fl uorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA125USI 60 HZ GEN. • OPERATION AND PARTS MANUAL — REV. #1 (03/25/11) — PAGE 25

Page 25
Image 25
Multiquip DCA125USI manual Load Application, Single Phase Load, Three Phase Load

DCA125USI specifications

The Multiquip DCA125USI is a high-performance portable diesel generator renowned for its reliability, efficiency, and robust construction, making it an ideal choice for construction sites, events, and remote locations requiring continuous power. Engineered for durability, this generator features a solid and compact design that allows seamless transport while providing ample power to meet demanding applications.

One of the standout features of the DCA125USI is its powerful 125 kVA output, capable of supplying electricity to a wide range of equipment simultaneously. With a fuel-efficient Tier 4 compliant engine, this generator not only delivers high performance but also addresses environmental concerns through reduced emissions. Operating at low noise levels, the DCA125USI ensures a quieter work environment, making it suitable for urban areas and noise-sensitive locations.

In terms of technology, the DCA125USI is equipped with a state-of-the-art digital control panel that offers advanced monitoring capabilities, allowing users to easily track the generator's performance, fuel consumption, and overall health. This user-friendly interface simplifies operation and enhances the overall experience for users, whether they are seasoned professionals or first-time operators. Additionally, the generator is fitted with automatic voltage regulation (AVR), which provides stable power output, protecting connected equipment from voltage fluctuations.

Safety is a priority with the Multiquip DCA125USI, as evidenced by its comprehensive set of protection features, including low oil pressure shutdown, high-temperature shutdown, and overload protection. These safety mechanisms ensure the longevity of the engine and the generator's components while safeguarding connected equipment against potential damage.

Another notable characteristic is its large fuel tank, which allows for extended run times, reducing the need for frequent refueling. This feature is particularly beneficial in situations where access to fuel is limited or where continuous operation is critical.

In conclusion, the Multiquip DCA125USI is a versatile and dependable portable diesel generator, catering to a wide variety of applications. Its combination of high output, advanced technology, and robust safety features make it an excellent investment for contractors, event organizers, and anyone in need of reliable power in challenging environments. With this generator, users can have peace of mind knowing they have a powerful energy solution at their disposal.