ENGINE OPERATING PANEL

The defi nitions below describe the controls and functions of the Engine Operating Panel (Figure 5).

1.Panel Light — Normally used in dark areas or at night time. When activated, panel lights will illuminate. When the generator is not in use be sure to turn the panel light switch to the OFF position.

2.Panel Light Switch — When activated will turn on control panel light.

3.Preheat Lamp — As the engine cranks, this lamp will illuminate to indicate automatic preheating of the engine glow plugs. When the lamp turns off, this indicates that the preheat cycle is complte and the engine will start automatically.

4.Warning Lamp (Diagnostic Lamp) — When lit indicates a that a failure has occured in the engine control system.

5.Fuel Leak Detection Lamp — This lamp will illuminate when a leak in the fuel tank containment enclosure is detected.

6.Engine Speed Switch — This switch controls the speed of the engine (low/high).

7.Oil Pressure Gauge — During normal operation this gauge should read between 42 ~71 psi. (290~490 kPa). When starting the generator the oil pressure may read a little higher, but after the engine warms up the oil pressure should return to the correct pressure range.

8.WaterTemperature Gauge — During normal operation this gauge be should read between 167°~203°F (75° ~95°C

9.Charging Ammeter Gauge — Indicates the current being supplied by the engine’s alternator which provides current for generator’s control circuits and battery charging system.

10.Fuel Gauge — Indicates amount of diesel fuel available.

11.Tachometer — Indicates engine speed in RPM’s for 60 Hz operation. This meter should indicate 1800 RPM’s when the rated load is applied. In addition a built in hour meter will record the number of operational hours that the generator has been in use.

12.Auto START/STOP Engine Controller (ECU) — This controller has a vertical row of status LED's (inset), that when lit, indicate that an engine malfunction (fault) has been detected. When a fault has been detected the engine controller will evaluate the fault

and all major faults will shutdown the generator. During cranking cycle, the ECU will attempt to crank the engine for 10 seconds before disengaging.

If the engine does not engage (start) by the third attempt, the engine will be shutdown by the engine controller’s Over Crank Protection mode. If the engine engages at a speed (RPM's) that is not safe, the controller will shutdown the engine by initializing the Over Speed Protection mode.

Also the engine controller will shut down the engine in the event of low oil pressure, high coolant temperature, low coolant level, and loss of magnetic pickup. These conditions can be observed by monitoring the LED status indicators on the front of the controller

module.

A.MPEC Control Switch — This switch controls the running of the unit. If this switch is set to the OFF/ RESET position, the unit will not run. When this switch is set to the manual position, the generator will start immediately.

If the generator is to be connected to a building’s AC power source via an automatic transfer switch (isolation), place the switch in the AUTO position. In this position, should an outage occur, the automatic transfer switch (ATS) will start the generator automatically via the generator’s auto-start contacts connected to the ATS’s start contacts. Please refer to your ATS installation manual for further instructions for the correct installation of the auto-start contacts of the generator to the ATS.

B.Low Oil Pressure — Indicates the engine pressure has fallen below 15 psi (103 kPa). The oil pressure is detected using variable resistive values from the oil pressure sending unit.This is considered a major fault.

C.High Coolant Temperature — Indicates the engine temperature has exceeded 230°F (110°C).The engine temperature is detected using variable resistive values from the temperature sending unit. This is considered a major fault.

D.Overcrank Shutdown — Indicates the unit has attempted to start a pre- programmed number of times, and has failed to start.The number of cycles and duration are programmable. It is pre-set at 3 cycles with a 10 second duration. This is considered a major fault.

E.Overspeed Shutdown — Indicates the engine is running at an unsafe speed. This is considered a major fault.

F.Engine Running — Indicates that engine is running at a safe operating speed.

DCA125USI 60 HZ GEN. • OPERATION AND PARTS MANUAL — REV. #1 (03/25/11) — PAGE 21

Page 21
Image 21
Multiquip DCA125USI manual Fuel Gauge Indicates amount of diesel fuel available, Module

DCA125USI specifications

The Multiquip DCA125USI is a high-performance portable diesel generator renowned for its reliability, efficiency, and robust construction, making it an ideal choice for construction sites, events, and remote locations requiring continuous power. Engineered for durability, this generator features a solid and compact design that allows seamless transport while providing ample power to meet demanding applications.

One of the standout features of the DCA125USI is its powerful 125 kVA output, capable of supplying electricity to a wide range of equipment simultaneously. With a fuel-efficient Tier 4 compliant engine, this generator not only delivers high performance but also addresses environmental concerns through reduced emissions. Operating at low noise levels, the DCA125USI ensures a quieter work environment, making it suitable for urban areas and noise-sensitive locations.

In terms of technology, the DCA125USI is equipped with a state-of-the-art digital control panel that offers advanced monitoring capabilities, allowing users to easily track the generator's performance, fuel consumption, and overall health. This user-friendly interface simplifies operation and enhances the overall experience for users, whether they are seasoned professionals or first-time operators. Additionally, the generator is fitted with automatic voltage regulation (AVR), which provides stable power output, protecting connected equipment from voltage fluctuations.

Safety is a priority with the Multiquip DCA125USI, as evidenced by its comprehensive set of protection features, including low oil pressure shutdown, high-temperature shutdown, and overload protection. These safety mechanisms ensure the longevity of the engine and the generator's components while safeguarding connected equipment against potential damage.

Another notable characteristic is its large fuel tank, which allows for extended run times, reducing the need for frequent refueling. This feature is particularly beneficial in situations where access to fuel is limited or where continuous operation is critical.

In conclusion, the Multiquip DCA125USI is a versatile and dependable portable diesel generator, catering to a wide variety of applications. Its combination of high output, advanced technology, and robust safety features make it an excellent investment for contractors, event organizers, and anyone in need of reliable power in challenging environments. With this generator, users can have peace of mind knowing they have a powerful energy solution at their disposal.