OUTPUT TERMINAL PANEL FAMILIARIZATION

120 VAC GFCI Receptacles

There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) receptacles provided on the output terminal panel. These receptacles can be accessed in any voltage change-over board configuration. Each receptacle is protected by a 20 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the U, V, and W output terminal lugs.

Pressing the reset button resets the GFCI receptacle after being tripped. Pressing the test button (See Figure 7) in the center of the receptacle will check the GFCI function. Both receptacles should be tested at least once a month.

Figure 7. G.F.C.I. Receptacle

Twist Lock Dual Voltage 120/240 VAC Receptacles

There are three 240/139V, 50 amp auxiliary twist-lock (CS- 6369) receptacles (Figure 8) provided on the output terminal panel. These receptacles can only be accessed when the voltage change-over board is configured for single-phase 240/120 application

Figure 8. 240/139V Twist-Lock Auxiliary

Receptacles

Each auxiliary receptacle is protected by a 50 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) on all three receptacles is dependent on the load requirements of the output terminal lugs.

Turn the voltage regulator control knob (Figure 9) on the control panel to obtain the desired voltage.Turning the knob clockwise will increase the voltage, turning the knob counter-clockwise will decrease the voltage.

Figure 9. Voltage Regulator Control Knob

DCA220ssCU/4i 60 hz generator• operation manual — rev. #0 (10/25/12) — page 21

Page 21
Image 21
Multiquip DCA220SSCU4i manual VAC Gfci Receptacles, 139V Twist-Lock Auxiliary Receptacles