GENERATOR START-UP PROCEDURE (MANUAL)
Before Starting
CAUTION
The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.
WARNING
NEVER manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.
1.Place the main, G.F.C.I., and aux. circuit breakers (Figure 35) in the OFF position prior to starting the engine.
Figure 35. Main, Aux. and GFCI
Circuit Breakers (OFF)
2.Make sure the voltage
3.Connect the load to the receptacles or the output terminal lugs as shown in Figure 10. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.
4.Tighten terminal nuts securely to prevent load wires from slipping out.
5.Close all engine enclosure doors (Figure 36).
CORRECT INCORRECT
Figure 36. Engine Enclosure Doors
Starting (Manual)
1.Place the engine speed switch (Figure 37) in the LOW (down) position.
Figure 37. Engine Speed Switch (Low)
2.Place the
Figure 38. Auto-Off/Reset Manua;Switch
(Manual Position)
NOTICE
If engine fails to start in a specified number attempts, the shutdown lamp will illuminate and the
NOTICE
Engine will
3.Once the engine starts, let the engine run for
Figure 39. Engine Speed Switch (High)
4.The generator’s frequency meter (Figure 40) should be displaying the 60 cycle output frequency in HERTZ.
Figure 40. Frequency Meter