GENERATOR OUTPUTS

Generator Output Voltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by applying jumpers (6) to the voltage change-over board (Figure 12). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regulator (VR) control knob located on the control panel.

Voltage Change-Over Board

The voltage change-over board (Figure 12) is located on the control box, behind the generator control panel. This board has been provided for ease of voltage selection.

Maximum Amps

Table 8 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed.

Table 8. Generator Maximum Amps

Model

DCA220SSCU/

DCA220SSCU4i

 

Rated Voltage

Maximum Amps

 

 

Single Phase 120 Volt

488.9 amps (4 wire)

 

 

Single Phase 240 Volt

244.4 amps (4 wire)

 

 

Three Phase 240 Volt

529 amps

 

 

Three Phase 480 Volt

264 amps

 

 

Figure 12. Voltage Change-Over Board

CAUTION

NEVER attempt to place jumper plates on the voltage change-over board while the generator is in operation. There exist the possibility of electrocution, electrical shock or burn, which can cause severe bodily harm or even death!

Table 7. Voltages Available

UVWO Output

Voltage Change-Over Board

Voltage Change-Over Board

Terminal Lugs

3-Phase 240/139V Position

3-Phase 480/270V Position

 

 

 

 

 

 

 

Line-Line

208V

220V

240V

416V

440V

480V

 

 

 

 

 

 

 

Line-Neutral

120V

127V

139V

240V

254V

277V

 

 

 

 

 

 

 

Voltage Change-Over Board Single-Phase 240/120V Position

 

Line-Neutral/

Line-Line

120V

Line-Neutral

N/A

N/A

240V

Line-Line

N/A

N/A

page 24 — dca220sscu/4i 60 hz generator • operation and Parts manual — rev. #0 (10/25/12)