DCA800SSK2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (09/03/09) — PAGE 23
OUTPUT TERMINAL PANEL FAMILIARIZATION

Twist Lock Dual Voltage 240/139 VAC Receptacles

There are three 240/139V, 50 amp auxiliary twistlock
(CS6369) receptacles (Figure 7) provided on the output
terminal panel..
240/139V TwistLock Auxiliary Figure 7.
Receptacles
Each auxiliary receptacle is protected by a 50 amp
circuit breaker. These breakers are located directly above
the auxiliary receptacles. Remember the load output
(current) on all three receptacles is dependent on the load
requirements of the Output Terminal Lugs.
Turn the voltage regulator control knob (Figure 8) on the
control panel to obtain the desired voltage. Turning the knob
clockwise will increase the voltage, turning the knob
counterclockwise will decrease the voltage.
Voltage Regulator Control KnobFigure 8.

Connecting Loads

Loads can be connected to the generator by the Output
Terminal Lugs or the convenience receptacles (Figure 9).
Make sure to read the operation manual before attempting
to connect a load to the generator.
To protect the output terminals from overload, a 3pole,
2500A main circuit breaker is provided. Make sure to switch
ALL circuit breakers to the OFF position prior to starting
the engine.
Connecting LoadsFigure 9.

Over Current Relay

An over current relay (Figure 10) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the reset button on the over
current relay must be pressed. The over current relay is
located in the control box.
Over Current RelayFigure 10.