LOAD APPLICATION

SINGLE PHASE LOAD

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is infl uenced by the effi ciency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Singlephase induction motors

 

 

0.40.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.40.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

THREE PHASE LOAD

When calculating the power requirements for 3phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motordriven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fl uorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

PAGE 24 — DCA800SSK2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (09/03/09)

Page 24
Image 24
Multiquip DCA800SSK2 manual Load Application, Single Phase Load, Three Phase Load

DCA800SSK2 specifications

The Multiquip DCA800SSK2 is a robust and versatile portable diesel generator, designed to meet the demands of a wide range of applications. With a powerful 800 kW (kilowatt) capacity, it is particularly suited for use in construction sites, events, and emergency backup power situations. This generator combines reliability, durability, and ease of use, making it a popular choice among contractors and rental companies.

One of the main features of the DCA800SSK2 is its advanced sound attenuation technology. This ensures that the generator operates quietly, minimizing noise pollution while maximizing performance. The enclosure is designed to reduce sound levels without compromising on the cooling requirements, which extends the overall lifespan of the generator. Users can expect noise levels well within acceptable limits for urban and residential areas.

The DCA800SSK2 is equipped with a state-of-the-art digital controller that offers enhanced monitoring and diagnostic capabilities. This intelligent control system enables users to track key performance metrics, such as voltage, frequency, and operating hours, all from a user-friendly interface. Furthermore, it includes automatic shutdown features for low oil pressure, high temperature, and overcurrent situations, providing an added layer of safety and preventing potential damage.

Fuel efficiency is another standout characteristic of the Multiquip DCA800SSK2. With a large fuel tank, it can operate for extended periods without frequent refueling, making it ideal for long-term use in remote areas where access to fuel may be limited. The generator's engine is engineered to provide optimal fuel consumption, ensuring that operators can maximize their running time while minimizing operational costs.

The DCA800SSK2 includes multiple outlets for electricity distribution, allowing users to connect various tools and equipment simultaneously. This versatility makes it suitable for a wide range of applications, from powering heavy machinery on construction sites to providing backup power for critical infrastructure.

Overall, the Multiquip DCA800SSK2 stands out in the market for its combination of power, efficiency, and advanced features. With its robust build quality, innovative technologies, and user-centric design, it is an excellent choice for anyone in need of a reliable portable generator. Whether for professional use or emergency situations, the DCA800SSK2 delivers outstanding performance and peace of mind.