Outdoor Installation

Install the generator in a location where it will not be exposed to rain or sunshine. Make sure the generator is on secure level ground so it cannot slide or shift around. Also install the generator so the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to the engine parts and alternator.

CAUTION :

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

TLG-12SPX — INSTALLATION

CAUTION :

An electric shock may happen when vibrators are used. Pay close attention to handling when operating vibrators and always use rubber boots and gloves to insulate the body from electrical shock.

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 13) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.

NOTE

When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.

PAGE 30 — TLG-12SPX — PARTS AND OPERATION MANUAL (STD) — REV. #4 (03/08/05)

Page 30
Image 30
Multiquip operation manual TLG-12SPX Installation, Outdoor Installation, Indoor Installation

TLG-12SPX specifications

The Multiquip TLG-12SPX is a state-of-the-art generator designed to meet the demanding needs of various industries including construction, events, and emergency backup power. With its impressive combination of power output, durability, and advanced features, it has become a popular choice among professionals requiring reliable energy solutions.

One of the standout features of the TLG-12SPX is its robust power generation capability. It offers a maximum output of 12,000 watts, making it suitable for powering heavy-duty tools, multiple appliances, and large equipment. This makes it an ideal solution for construction sites where high power demands are common. The generator is equipped with a professional-grade, heavy-duty engine that ensures optimal performance under various loads.

The TLG-12SPX is also designed with mobility and ease of use in mind. Its compact design, combined with a rugged frame and sturdy wheels, allows for easy transport across job sites. The generator features a user-friendly control panel that provides easy access to power management functions and monitoring, allowing users to quickly assess output levels and operational status.

Another notable technology integrated into the TLG-12SPX is its advanced noise reduction system. This generator operates at a significantly lower noise level compared to traditional models, making it a great option for events where noise restrictions are a concern. The low decibel operation enhances user comfort and ensures compliance with local noise ordinances.

In terms of safety features, the TLG-12SPX is built with multiple safeguards. It includes an automatic low oil shutdown, which protects the engine by halting operation when oil levels are too low. Additionally, there are circuit breakers to prevent overload situations, ensuring that the generator operates safely even under heavy loads.

The fuel efficiency of the TLG-12SPX is another impressive aspect. It is designed to maximize operational time with minimal refueling, making it an efficient choice for both short-term and extended needs. This not only reduces operational costs but also enhances productivity by minimizing downtime due to fuel management.

Overall, the Multiquip TLG-12SPX generator stands out due to its powerful output, advanced noise reduction technology, user-friendly controls, and enhanced safety features. These characteristics make it a top choice for professionals seeking a reliable and efficient power source across a range of applications.