TLG-12SPX4 —TROUBLESHOOTING (GENERATOR)

TLG-12SPX4 —TROUBLESHOOTING (GENERATOR)

Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a breakdown, use Table 17 shown below for diagnosis of the generator. If the problem cannot be remedied, consult our company's business office or service plant.

TABLE 17. GENERATOR TROUBLESHOOTING

SYMPTOM

POSSIBLE PROBLEM

SOLUTION

 

 

 

No Voltage Output
AC Voltmeter defective?
Check output voltage using a voltmeter.

 

 

 

 

Is wiring connection loose?
Check wiring and repair.

 

 

 

 

Is AVR defective?
Replace if necessary.

 

 

 

 

Defective Rotating Rectifier?
Check and replace.

 

 

 

 

Defective Exciter Field?
Check for 17.3 ohms across J & K on CN1

 

 

 

Low Voltage Output
Is engine speed correct?
Turn engine throttle lever to "High".

 

 

 

 

Is wiring connections loose?

Check wiring and repair.

 

 

 

 

Defective AVR?

Replace if necessary.

 

 

 

High Voltage Output

Is wiring connections loose?

Check wiring and repair.

 

 

 

 

Defective AVR?

Replace if necessary.

 

 

 

Circuit Breaker Tripped
Short Circuit in load?
Check load and repair.

 

 

 

 

Over current?
Confirm load requirements and reduce.

 

 

 

 

Defective circuit breaker?

Check and replace.

 

 

 

 

Over current Relay actuated?
Confirm load requirement and replace.

 

 

 

TLG-12SPX4— OPERATION AND PARTS MANUAL — REV. #1 (12/17/09) — PAGE 41