SYMPTOM |
| PROBLEM |
| TEST SOLUTION |
| ||
|
|
|
|
| |||
|
|
|
|
| |||
Pilot burning; no | Themostat or switch is de- | - | connect a jumper wire across the wall switch terminals; if main |
| |||
gas | to | main | fective. | burner lights, replace switch / thermostat. |
| ||
burner; gas knob | Wall switch wiring is defec- | - | disconnect switch wires &connect a jumper wire across terminals |
| |||
is on | 'HI'; | wall | tive. | 1 & 3; if the main burner lights, check the wires for defects and / or |
| ||
switch / thermostat |
|
| replace wires. |
| |||
is on. |
|
|
|
|
| ||
|
| Main burner orifice is plugged. | - | remove stoppage in orifice. |
| ||
|
|
|
| ||||
|
|
| Faulty valve. | - | replace. |
| |
|
|
|
|
|
|
|
|
Pilot | goes | out | Gas piping is undersized. | - | turn on all gas appliances and see if pilot flame flutters, dimin- |
| |
while | standing; |
|
| ishes or extinguishes, especially when main burner ignites. Monitor |
| ||
Main burner is in |
|
| appliance supply working pressure. |
| |||
'OFF' position. |
|
| - | check if supply piping size is to code. Correct all undersized piping. |
| ||
|
|
|
|
|
| ||
Pilot will not light. |
| No spark at pilot burner | - | check if pilot can be lit by a match |
| ||
|
|
|
|
| - | check that the wire is connected to the push button ignitor. |
|
|
|
|
|
| - | check if the push button ignitor needs tightening. |
|
|
|
|
|
| - | replace the wire if the wire insulation is broken or frayed. |
|
|
|
|
|
| - | replace the electrode if the ceramic insulator is cracked or broken. |
|
|
|
| Out of propane gas | - | replace the push button ignitor. |
| |
|
|
| - | fill the tank. |
| ||
|
|
|
|
|
|
|
|
|
|
| Spark gap is incorrect | - | spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.) from |
| |
|
|
|
|
| the electrode tip and the pilot burner. To ensure proper electrode |
| |
|
|
|
|
| location, tighten securing nut (finger tight plus 1/4 turn). |
| |
|
|
| No gas at the pilot burner | - | check that the manual valve is turned on. |
| |
|
|
|
|
| - | check the pilot orifice for blockage. |
|
|
|
|
|
| - | replace the valve. |
|
|
|
|
|
| - | call the gas distributor. |
|
Main burner goes | Pilot flame is not large | - | turn up pilot flame. |
| |||
out; pilot stays on. | enough or not engulfing the | - replace pilot assembly. |
| ||||
|
|
| thermopile |
|
|
| |
|
|
| Thermopile shorting | - clean thermopile connection to the valve. Reconnect. |
| ||
|
|
|
|
| - replace thermopile / valve. |
| |
|
|
| Remote wall switch wire is | - | shorten wire to correct length or wire gauge. |
| |
|
|
| too long; too much resis- |
|
|
| |
|
|
| tance in the system. |
|
|
| |
|
|
|
|
|
|
|
|
|
|
| Faulty thermostat or switch. | - | replace. |
|
Main burner goes out; pilot goes out.
Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON"
Vent is blocked | - | check for vent blockage. |
|
|
|
Vent is | - | check joint seals and installation. |
|
|
|
4" flexible vent has become | - | |
disconnected from fireplace. |
|
|
Remote | wall | Wall switch is mounted up- | - reverse. | |
switch is in "OFF" | side down |
| ||
position; | main | Remote wall switch is | - replace. | |
burner comes on | grounding. |
| ||
when gas knob is |
|
| ||
Remote wall switch wire is | - check for ground (short); repair ground or replace wire. | |||
turned to "ON" po- | ||||
sition. |
| grounding. |
| |
| Faulty valve. | - replace. | ||
|
| |||
|
|
|
| |
|
|
|
| |
|
|
|
|