Napoleon Fireplaces GD70NT-S Using Flexible Vent Components, Horizontal Air Terminal Installation

Models: GD70PT-S GD70NT-S

1 28
Download 28 pages 19.04 Kb
Page 12
Image 12
USING FLEXIBLE VENT COMPONENTS

12

USING FLEXIBLE VENT COMPONENTS

Use only approved aluminum flexible liner kits marked

"Wolf Steel Approved Venting" as identified by the stamp only on the 7" outer liner.

For optimum performance it is recommended that all horizontal runs have a minimum ¼ inch rise per foot using flexible venting.

HORIZONTAL AIR TERMINAL INSTALLATION

1.Stretch the 4" diameter aluminum flexible liner to the required length taking into account the additional length needed for the finished wall surface. Apply a heavy bead of the high temperature sealant Mill Pac, to the inside of the 4" liner approximately 1" from the end. Slip the liner a mini- mum of 2" over the fireplace vent collar and secure with 3 #8 screws.

2.Using the 7" diameter flexible aluminum liner, apply seal- ant, slide a minimum of 2" over the fireplace combustion air collar and secure with 3 #8 screws.

3.Insert the liners through the firestop. Position and se- cure the fireplace using the nailing tabs (2 per side) and/or secure to the floor using screws inserted through the two ¼" diameter holes in the front left and right corners of the base. The liners should be flush with the exterior wall.

The air terminal may be recessed into the exterior wall or siding by 1½", the depth of the return flange.

FIGURE 18

FIGURE 19

4.From outside, apply a bead of the high temperature seal- ant to the inside of both liners, approximately 1" from the end of each liner.

5.Holding the air terminal (lettering in an upright, readable position), insert into both liners with a twisting motion to ensure that both the terminal sleeves engage into the lin- ers / sealant. Secure the terminal to the exterior wall and make weather tight by sealing with caulking (not supplied).

6.If more liner needs to be used to reach the fireplace, couple them together as illustrated in FIGURE 13. The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use Napoleon support ring assembly W010-0370or equivalent noncombustible strapping to maintain the minimum 1" clearance to com- bustibles.

W415-0434 / C / 03.24.05

For safe and proper operation of the fireplace, follow the venting instructions exactly.

All inner exhaust and outer intake vent pipe joists may be sealed using either Red RTV high temp silicone seal- ant or Black high temp Mill Pac with the exception of the fireplace exhaust flue collar which must be sealed us- ing Mill Pac (not supplied).

VERTICAL AIR TERMINAL INSTALLATION

1. Fasten the roof support to the

FIGURE 20

roof using the screws pro-

 

vided. The roof support is

 

optional. In this case the

 

venting is to be ad-

 

equately supported us-

 

ing either an alternate

 

method suitable to the

 

authority having jurisdic-

 

tion or the optional roof

 

support.

 

2. Stretch the 4" diameter alumi-

FIGURE 21

num flexible liner to the required

 

length. Slip the liner a minimum

 

of 2" over the inner sleeve of the

 

air terminal and secure with 3 #8

 

screws. Seal using a heavy bead

 

of the high temperature sealant.

 

3.Repeat using 7" diameter alu- minum flexible liner.

4.Thread the air terminal pipe as- sembly down through the roof.

The air terminal must be located vertically and plumb. At- tach the air terminal assembly to the roof support, ensur- ing that a minimum 16" of air terminal will penetrate the roof when fastened.

DO NOT CLAMP THE

FLEXIBLE ALUMINUM

LINER.

5.Remove nails from the shingles, above and to the sides of the chimney. Place the flashing over the air ter-

minal and slide it un- FIGURE 22 derneath the sides and

upper edge of the shingles. Ensure that the air terminal is properly centered within the flashing, giving a 3/4" margin all around. Fasten to the roof. Do not nail through the lower portion of the flashing. Make weather-tight by sealing with caulking. Where possible, cover the sides and top edges of the flashing with roofing material.

6.Apply a heavy bead of weatherproof caulking 2 inches above the flashing. Slide the storm collar around the air terminal and down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved. Attach the other storm collar centered between the air intake and the air exhaust slots onto the air termi- nal. Tighten securely. Attach the vertical rain cap.

Page 12
Image 12
Napoleon Fireplaces GD70NT-S, GD70PT-S Using Flexible Vent Components, Horizontal Air Terminal Installation, Figure Figure