Chapter 3 Signal Connections
© National Instruments Corporation 3-5 DAQCard-1200 User Manual
How you connect analog input signals to the DAQCard-1200 depends on
how you configure the card analog input circuitry and the type of input
signal source. With different DAQCard-1200 configurations, you can use
the instrumentation amplifier in different ways. Figure 3-2 shows a diagram
of the DAQCard-1200 instrumentation amplifier.
Figure 3-2. DAQCard-1200 Instrumentation Amplifier
Table 3-1. Bipolar and Unipolar Analog Input Signal Range Versus Gain
Gain Setting
Input Signal Range
Bipolar Unipolar
1±5 V 0 to 10 V
2±2.5 V 0 to 5 V
5±1 V 0 to 2 V
10 ±500 mV 0 to 1 V
20 ±250 mV 0 to 500 mV
50 ±100 mV 0 to 200 mV
100 ±50 mV 0 to 100 mV
V
V
+
Instrumentation
Amplifier
in+
in
+
Measured
Voltage
Vm
Vm = [Vin + – Vin –] GAIN