Nordyne M3RL Ventilation, Start-Upand Adjustments, General, Low Voltage Field, Start-UpProcedure

Models: M3RL

1 36
Download 36 pages 56.96 Kb
Page 26
Image 26
VENTILATION

The thermostat must not be installed on an outside wall or any other location where its operation may be adversely affected. Adverse affects include radiant loading from fireplaces, sunlight, or lighting fixtures, and convective loading from warm air registers or electrical appliances.

To check the heat anticipator setting either:

1.Add the current draw of the system com- ponents; or

2.Measure the current flow on the thermostat R-W circuit after the circulating blower motor has started.

Set the heat anticipator according to the ther- mostat manufacturer's instructions for heat anticipator settings.

VENTILATION

Ventilation must be provided for homes built to HUD Manufactured Homes Safety and Con- struction Standards. This ventilation can be sup- plied by the VentilAire III or VentilAire IV acces- sories. (See Table 12). Alternate means to pro- vide the ventilation air must meet the require- ments of all applicable local and federal codes.

For installation of the VentilAire III or IV, follow the instructions provided with the VentilAire kit.

START-UP AND ADJUSTMENTS

General

Prior to start-up, verify that:

1.The line voltage power leads are securely connected, that the polarity of the con- nections is correct, and that the furnace is properly grounded.

2.The thermostat wires (R, W, Y, and G) are securely connected to the correct leads on the terminal strip of the circuit board.

3.The natural gas line service pressure must not exceed 10.0 in. water column (0.36 psig), and must not be less than 4.5 in. water column (0.16 psig). For LP gas the line service pressure must not exceed 14 in. water column (0.51 psig), and must not be less than 11.0 in. W.C. (0.40 psig).

26

 

 

 

 

 

A/C Condensing Unit

 

 

 

 

 

 

 

 

 

Condensing Unit

 

 

 

 

 

 

 

 

 

 

 

Control Box

 

 

 

 

 

 

 

 

 

 

COM

 

 

Blower Off

60 90

120 180

 

 

R

 

 

3 Amp

 

Timing

 

R

 

 

 

 

 

 

Connect

C

 

24 V

 

Fuse

 

 

 

TWIN

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

R & W

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flame Signal Light

 

 

Heating

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

(Yellow)

 

 

Only

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Room

W

 

 

 

 

 

Status Light

 

 

 

 

 

 

 

 

 

 

9

6

3

 

 

 

 

 

(Red)

 

 

Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

5

2

 

 

 

 

 

 

 

 

 

 

 

7

4

1

 

 

 

 

 

 

 

 

 

NOTE: The "Y"

 

 

 

 

 

 

 

 

 

 

 

 

terminal on the

 

 

 

 

 

 

 

 

 

 

 

 

UTEC control board

 

 

 

 

 

 

 

 

 

 

 

 

must be connected

EAC

 

 

 

 

 

 

 

 

 

 

 

to the thermostat

 

 

 

 

 

 

 

 

 

 

 

for proper cooling

 

Neutrals

 

 

 

 

 

 

 

mode operation.

HUM

 

 

 

 

 

 

 

 

FIELD WIRING

 

 

Unused Motor Leads

 

 

 

 

 

6

3

HUM

 

COOL

HEAT

XFMR EAC

 

 

 

Low Voltage

 

 

M3 M2 M1

 

L1

 

 

 

5

2

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

1

 

 

 

 

 

 

 

 

Figure 28. Low Voltage Field,

Four-wire Heating/Cooling Applications

4.The roll-out and vent safety manual reset switches are closed. If necessary, press the red button to reset a switch. See Figure 26 for location. DO NOT install a jumper wire across a switch to defeat its function. If a switch reopens on start-up, DO NOT reset the switch without identify- ing and correcting the fault condition which caused the switch to trip.

5.The blower door is in place, closing the door switch in the line voltage circuit.

6.The gas line has been purged and all connections are leak tight.

Start-Up Procedure

1.Set the thermostat to the lowest setting.

2.Close the disconnect(s) to provide line voltage to the furnace.

3.Follow the procedures given on the oper- ating instructions label attached to the furnace.

4.Set the thermostat above room tempera- ture and verify the sequence of operation. (See the SEQUENCE OF OPERATION.)

Page 26
Image 26
Nordyne M3RL Ventilation, Start-Upand Adjustments, General, Low Voltage Field, Four-wireHeating/Cooling Applications