| 20 |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| |
|
| REAR WALL OF CLOSET OR ALCOVE |
| |||
|
|
| OUTLINE |
|
| |
|
|
| FLOOR |
|
| |
|
|
| FOR DUCT CONNECTIONS | FURNACE |
|
|
|
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
24 |
|
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
| VENT |
| |
|
|
|
|
|
| |
|
|
|
|
| COMBUSTION AIR INTAKE | |
|
|
|
|
| FUEL LINE ENTRY |
|
|
|
|
|
| 2 |
|
|
|
| 10 |
|
|
|
| ˚ |
|
| |||
|
|
|
| |||
| ALT FUEL LINE |
| FURNACE |
| ||
|
| ENTRY |
|
| ||
|
|
|
| OUTER DOOR |
| |
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
| FLOOR |
|
|
|
|
|
| FOR OPTIONAL |
|
|
|
|
|
| COOLING COIL |
|
|
|
|
|
| FOR |
|
|
|
|
|
| SERIES UNITS |
|
|
|
Figure 7. Cut-Out Locations
AIR DISTRIBUTION SYSTEMS
For proper air distribution, the supply duct system must be designed so that the static pressure measured external to the furnace does not exceed the listed static pressure rating shown on the furnace rating plate.
Three typical distribution systems are illus- trated in Figure 2. Location, size, and number of registers should be selected on the basis of best air distribution and floor plan of the home.
DUCT CONNECTOR SELECTION
PLATINUM SERIES
a. For Platinum ready construction use the 14” round plenum, p/n: 903896.
NON-PLATINUM SERIES
a. Determine depth of floor cavity from surface of floor to top of supply air duct (See Figure 3).
b. Select appropriate model from Table 5 which matches
10
cavity. To maximize air delivery, re- move reducer “C” (see Figure 5) to obtain the largest open area that will fit the duct/floor construction.
DUCT INSTALLATION
Required floor, ceiling, and roof
CUT OUT FLOOR OPENING & FUEL LINE HOLE
a. Determine center of closet or alcove (Fig- ures 7 & 8).
b. Locate center of the floor opening, mea- sured 10" from the rear wall, and mark cut- out measuring approximately
c.Locate center of gas line hole, measured 23- 1/4" from the rear wall and