Omega 1002 manual Analog Input Signal Connection

Models: 1002

1 48
Download 48 pages 45.53 Kb
Page 19
Image 19

2.6 Analog Input Signal Connection

The OME-PCI-1002 can measure signals in the single-ended or differential mode. In the differential mode each channel has a unique signal HIGH and signal LOW connection. In the single-ended mode all channels have a unique signal HIGH connection but share a common LOW or ground connection. Differential connections are very useful for low level signals (millivolt), since they better reject electrical noise that can affect the quality of the measurement. A differential connection is also necessary when a common ground is unacceptable. The benefit of using a single-ended connection is that twice the number of channels is available. In general, a single-ended connection is often a good choice when working with higher level signals (5V or 10V for example), especially if the signal is coming from an isolated device such as a signal conditioner. Several different types of wiring diagrams are discussed below.

Figure 2-3A shows a differential connection to a grounded source. If the source is grounded, making a second connection to the card’s ground could cause a ground loop resulting in erroneous data. It is important to note that the maximum common mode voltage between the input source and AGND is 70Vp-p. If the card is connected to a source with a common mode voltage greater than 70Vp-p, the input multiplexer will be permanently damaged! When measuring common mode voltage, it is best to use an oscilloscope rather than a multi-meter.

Figure 2-3B shows a differential connection to a floating source. In such cases a connection should be made between the low channel input and analog ground.

Figure 2-4 shows connection of multiple sources in single-ended mode. This connection assumes creating one common ground will not cause a problem. This is normally the case when connecting to devices that are isolated or floating.

Figure 2-5 demonstrates how to connect bridge transducers. Bridge transducers include strain gauges, load cells and certain type of pressure transducers. The diagram assumes that there is a single external power supply providing power to the bridge. Each bridge is connected to a differential channel. No connection is made between channel low and analog ground. A connection should be made between analog ground and the negative of the power supply. An isolated power supply is strongly suggested.

Figure 2-6 demonstrates how to connect a 4-20mA current loop. Since the card reads voltages, the current is converted to voltage by passing it through a shunt resistor. By Ohms law (V=IR), when using a 250Ω resistor, 4 mA will be converted to 1V and 20mA to 5V. If the source is linear, the output voltage range will also be linear.

19

Page 19
Image 19
Omega 1002 manual Analog Input Signal Connection