Chapter 3: Quick Start
19Step 4: Set Temperature Limits
High and low temperature limits can be separately programmed
for each input that is configured as temperature. Limits can
range from –20° to +150° Fahrenheit, or from –30° to 65°
Celsius. Default settings are: 10° F for low temperature and
100° F for high temperature. Do not set temperature limits too
close to normal room temperature, since minor fluctuations
could result in frequent and unnecessary alarm dialouts.
1. Press SET.
SET
#
2. Press TEMP LIMITS.
5
TEMP LIMITS
3. From the number keys, press a number (from 1 to 4) that
corresponds to the temperature input being programmed.
1
CALL
DELAY
2
VOICE
REPS
3
INTERCALL
TIME
4
MAX CALLS
The OMA-P1104 responds: “Enter low temperature
limit.”
4. Using the number keys, enter a value for low temperature
limit. The OMA-P1104 will recite the digits as they are
pressed. If a negative number is required, first press
PAUSE, then enter the number.
1
CALL
DELAY
2
VOICE
REPS
3
INTERCALL
TIME
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
7
RECOGNITION
TIME
8
CLOCK
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
5. Press ENTER.
ENTER
TONE
PM
ENTER
TONE
PM