HUMIDITY

(OMWT-TEMPRH) [Devicen] - Section name.

Address - – serial number of the sensor.

DeviceType - Device type. (DeviceType=HUMIDITY)

PollTime - How often to poll the device. (ms)

Label - Name used for the device (and Topic).

Log - Enable/disable logging of device.

LogDecimalPlaces - Number of decimals to create when logging. PollSamples - No. of samples per poll (must be odd no.) If >0 Median Filter

if <0 then Average Filter is used.

Temperature - Indicates if sensor needs temperature compensation. (0 or 1).

DwellTime - Time allowed to charge the probe. (ms) PostDwell - Time after reading to allow bus to recover. (ms) OverSampleDwell - Time before each over sample to charge probe. (ms) DeadBand - Dead band filtering value in % of full scale.

Description - General purpose description.

Cal1Raw - Two point calibration point 1.

Cal2Raw - Two point calibration point 2.

Cal1Engr - Two point calibration engineering units for point 1.

Cal2Engr - Two point calibration engineering units for point 2.

Units - % Relative Humidity

TempCoeff - PPM temperature coefficient of the sensor. TempCalib - Temperature at which the calibration was done. TempAddress – serial number of the temperature sensor in the probe. MacroFilterElements - running macro filter of the sampled data. Syntax:

[no. of elements, type] where no. of elements is number of samples to filter; type – “AVERAGE”, “MEDIAN” and “AVERAGEMEDIAN”. Default is “=3,MEDIAN”. Example: FilterElements1=6,AVERAGE CorrID – What CorrectionID to use with this device. Must be found in the

"Correction.INI" file that you write and keep in the same directory as the OMWT-SOFT-OPC.ini file. 0 is the default and means no correction; 127 is the maximum.

OMWT-SOFT-OPC Server

OMWT-SOFT-OPC Server .ini File Format N 19