1.8Termination Bus

In order to avoid signal reflections on the bus, each bus segment has to be blanked off at its physical beginning and at its end with the characteristic impedance. A termination resister (Rt) is installed for this purpose. The Rt value - 120Ω ± 2% is recommended, and the detailed connection of Rt can be referred from the “Terminator Connection” diagram below.

Host

Data+

120 ohms

Data-

Data+

120 ohms

Data-

Terminator Connection

1.9.Shielding

In case of increased interference, a shielded bus cables is recommended to use for wiring between module and modules. In addition, a shielding also should be done for the cable of power supply and for the signal cables.

Some experiences and recommendations are concerning for shield connection.

1.The shield should be connected with protective earthing at each bus connection.

2.The shield should be applied additionally several times along the course of the cable.

3.The Computer should be applied the shield directly to the appliance or to separate shield rails.

braided shield

EarthingPoint

Isolation

RS-485 Connection

DA DA

TA TA

+ -

OMR-Module

1-6 Introduction

Page 8