319
SYSMAC NET Link Systems The destination port number is always set to 0. Set the destination node numberto 0 to send the data to all nodes. Set the network number to 0 to send data to anode on the same Subsystem (i.e., network). Refer to the SYSMAC NET LinkSystem Manual for details.
Word Bits 00 to 07 Bits 08 to 15
CNumber of words (0 to 1000 in 4-digit hexadecimal, i.e., 0000hex to 03E8hex)
C+1 Network number (0 to 127 in 2-digit
hexadecimal, i.e., 00hex to 7Fhex)Bit 12 ON: Direct destination
beginning word
designation
OFF: Indirect designation
Bit 14 ON: Operating level 0
OFF: Operating level 1
Bits 08 to 11, 13 and 15: Set to 0.
C+2 Destination node (0 to 126 in 2-digit
hexadecimal, i.e., 00hex to 7Ehex)* Destination port
NSB: 00
NSU: 01/02
*The node number of the PC executing the send may be set.
SYSMAC LINK Systems Set the destination node number to 0 to send the data to all nodes. Refer to theSYSMAC LINK System Manual for details.
Word Bits 00 to 07 Bits 08 to 15
CNumber of words (0 to 1000 in 4-digit hexadecimal, i.e., 0000hex to 03E8hex)
C+1 Response time limit (0.1 and 25.4
seconds in 2-digit hexadecimal
without decimal point, i.e., 00hex to
FFhex)
Note: The response time will be
2 seconds if the limit is set to 0hex.
There will be no time limit if the
time limit is set to FFhex.
Bits 08 to 11:
No. of retries (0 to 15 in
hexadecimal,
i.e., 0hex to Fhex)
Bit 12 ON: Direct destination
beginning word
designation
OFF: Indirect designation
Bit 13 ON: Response not
returned.
OFF: Response returned.
Bit 14 ON: Operating level 0
OFF: Operating level 1
Bit 15: Set to 1.
C+2 Destination node (0 to 62 in 2-digit
hexadecimal, i.e., 00hex to 3Ehex)* Set to 0.
*The node number of the PC executing the send cannot be set.
Network Instructions Section 5-26