464
10-3-7 AR AREA READ –– RJ

Reads the contents of the specified number of AR words, starting from the speci-

fied word.

Command Format
@RJ
FCS
x 101x 100x 103x 102
x 101x 100x 103x 102x 101x 100
TerminatorBeginning word
(0000 to 0027)
Node no. Header
code No. of words
(0001 to 0028)
Response Format
@RJ
FCS
x 101x 100x 161x 160
x 163x 162x 161x 160
Node no. End codeHeader
code Read data (1 word )
Read data
(for number of words read)
Terminator

Limitations The text portion of the responses first frame can contain up to 30 words.

PC Settings

PC Mode UM Area

RUN MONITOR PROGRAM Write-protected Read-protected

OK OK OK OK OK

Execution Conditions

Commands Responses

Single Multiple Single Multiple

OK --- OK ---

End Codes An end code of 14 (format error) will be returned if the length of the command is

incorrect and an end code of 15 (entry number data error) will be returned if the

specified words exceed the data area boundaries or arent specified in BCD.

End code Contents

00 Normal completion

13 FCS error

14 Format error

15 Entry number data error

18 Frame length error

10-3-8 EM AREA READ –– RE

Reads the contents of the specified number of EM words, starting from the spe-

cified word in the specified EM bank.

Command Format
@RE
FCS
x 101x 100x 103x 102
x 101x 100x 103x 102x 101x 100
Node no. Header
code TerminatorBeginning word
(0000 to 6143) No. of words
(0001 to 6144)
Bank no.
(See note.)
Bank No.

Note Input 00, 01, or 02 to specify bank number 0, 1, or 2. Input two spaces to specify

the current bank.

Host Link Commands Section 10-3