480
End code Contents
04 Address over
13 FCS error
14 Format error
15 Entry number data error
16 Command not supported
18 Frame length error
23 User memory protected
10-3-22 SV CHANGE 3 –– W%

Changes the contents of the second word of the TIM, TIMH(15), CNT,

CNTR(12), or TTIM(87) at the specified program address in the users program.

Command Format
@W%
OP4OP3OP2OP1
x 102
x 100
x 101x 105x 104x 103
x 100
x 103x 102x 101
x 101x 100OP4OP3OP2OP1 x 102
x 103x 101x 100
Node no. Program
address
Must be 0
Mnemonic Timer/counter
(0000 to 0511)
TerminatorFCS
Header
code
Operand SV

Use all four characters to specify the timer or counter instructions mnemonic.

Add a space to the end of a TIM or CNT mnemonic to make it 4 characters long.

Instruction name Mnemonic TC number
OP1 OP2 OP3 OP4 range
TIMER T I M (Space) 0000 to 0511
HIGH-SPEED TIMER T I M H
COUNTER C N T (Space)
REVERSIBLE COUNTER C N T R
TOTALIZING TIMER T T I M

The Operand parameter indicates the data area where the SV is stored or a

constant. The SV parameter indicates the word address or the SV itself if it is a

constant.

Operand Classification Constant or
OP1 OP2 OP3 OP4 word address
C I O (Space) IR or SR 0000 to 0511
L R (Space) (Space) LR 0000 to 0063
H R (Space) (Space) HR 0000 to 0099
A R (Space) (Space) AR 0000 to 0027
D M (Space) (Space) DM 0000 to 6655
D M (Space) DM (indirect) 0000 to 6655
C O N (Space) Constant 0000 to 9999
E M (Space) (Space) EM 0000 to 6143
E M (Space) EM (indirect) 0000 to 6143
Host Link Commands Section 10-3