486
Response Format
@KS
x 100
x 101x 161x 160
Node no. Header
code TerminatorFCSEnd code
Limitations Bits in SR 253 through SR 255 cant be specified.
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
--- OK OK OK OK
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK --- OK ---
End Codes An end code of 14 (format error) will be returned if the length of the command is
incorrect.
An end code of 15 (entry number data error) will be returned if the operand, word
address, or bit parameter setting is incorrect.
End code Contents
00 Normal completion
01 Not executable in RUN mode
13 FCS error
14 Format error
15 Entry number data error
18 Frame length error
10-3-27 FORCED RESET –– KR
Force resets an IR, SR, LR, HR, or AR bit or the Completion Flag of a timer or
counter. Once a bit has been forced set or reset, that status will be retained until
FORCED SET/RESET CANCEL (KC) is transmitted.
Command Format
@KR
x 100
x 101x 103x 102x 101x 100x 101x 100
OP1 OP2 OP3 OP4
Node no. Header
code TerminatorFCS
Operand Word
address Bit
For data areas IR, SR, LR, HR, and AR, the Operand parameter indicates the
data area where the bit will be force-set and the Word address parameter indi-
cates the word address.
Host Link Commands Section 10-3