490
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
--- OK OK OK OK
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK --- OK ---
End Codes An end code of 14 (format error) will be returned if the length of the command is
incorrect.
End code Contents
00 Normal completion
13 FCS error
14 Format error
18 Frame length error
10-3-30 PC MODEL READ –– MM

Reads the model type of the PC. The codes returned for this command are differ-

ent from the NT Link codes.

Command Format
@MM
x 100
x 101
Node no. Header
code TerminatorFCS
Response Format
@MM
x 100
x 101x 161x 160
x 161x 160
Node no. Header
code TerminatorFCSEnd code Model
code

Model code indicates the PC model in two digits hexadecimal.

Model code Model
01 C250
02 C500
03 C120
0E C2000
10 C1000H
11 C2000H/CQM1
12 C20H/C28H/C40H, C200H, C200HS, C200HX/HG/HE
20 CV500
21 CV1000
22 CV2000
40 CVM1-CPU01-E
41 CVM1-CPU11-E
42 CVM1-CPU21-E
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
OK OK OK OK OK
Host Link Commands Section 10-3