Klinkmann Automation Omron Ethernet DAServer | 36 |
Item/point names, corresponding to CIO Area, may be without prefix.
(*)Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U" ("u") or without suffix), for signed integers from
(**)Data cannot be written to addresses A000…A447 in the Auxiliary Area. (***) Current bank only (Memory Area code 98 in Hex).
(****) Extended memory bank 0 to bank C (in Hex), up to 13 banks supported depending on CPU type. The prefix Ez can be one of the following: EA, EB, EC, ED, EE, EF, EG, EH, EI, EJ, EK, EL or EM. For read operations (both for Bit status and Words) and for Word write operations the Memory Area codes A0…AC ( in Hex) are used. For Bit writing the Memory Area codes 20…2C (in Hex) are used.
(*****) Read only.
(******) Not supported on CJ1 controllers.
The following examples show the correct format for item names for CS1 and CJ1 PLCs:
CIO2:01 | - | CIO area (Bit status), word address 2, bit number 1. |
257 | - | CIO Area (Word contents), word address 257 |
H62.10 | - | Holding Area (Bit), word address 62, bit number 10 |
D21 | - | Data Memory Area with word address 21 |
EA12 | - | Extended Data Memory bank 0 word address 12 |
EC48.10 | - | Extended Data Memory bank 2 word address 48, bit number 10 |
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3 | 17014m13 |