Klinkmann Automation Omron Ethernet DAServer

36

Item/point names, corresponding to CIO Area, may be without prefix.

(*)Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U" ("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for long or 32-bit integer is from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default value range for Integer Tag Type is unsigned integer.

(**)Data cannot be written to addresses A000…A447 in the Auxiliary Area. (***) Current bank only (Memory Area code 98 in Hex).

(****) Extended memory bank 0 to bank C (in Hex), up to 13 banks supported depending on CPU type. The prefix Ez can be one of the following: EA, EB, EC, ED, EE, EF, EG, EH, EI, EJ, EK, EL or EM. For read operations (both for Bit status and Words) and for Word write operations the Memory Area codes A0…AC ( in Hex) are used. For Bit writing the Memory Area codes 20…2C (in Hex) are used.

(*****) Read only.

(******) Not supported on CJ1 controllers.

The following examples show the correct format for item names for CS1 and CJ1 PLCs:

CIO2:01

-

CIO area (Bit status), word address 2, bit number 1.

257

-

CIO Area (Word contents), word address 257

H62.10

-

Holding Area (Bit), word address 62, bit number 10

D21

-

Data Memory Area with word address 21

EA12

-

Extended Data Memory bank 0 word address 12

EC48.10

-

Extended Data Memory bank 2 word address 48, bit number 10

Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3

17014m13

Page 38
Image 38
Omron DR 170 14 manual Klinkmann Automation Omron Ethernet DAServer