The following table lists the supported item names for the C200HX, C200HG and C200HE PLCs.

Memory Area

Prefix

Tag Type

Address Range

Value

Range

Suffix

Internal Relay Area 1, 2

IR

Discrete

IR0:00...IR511:15

0, 1

 

Special Relay Area 1, 2

 

 

or

 

 

(Bit status)

 

 

0.00...511.15

 

 

Internal Relay Area 1, 2

IR

Integer

IR0... IR511

(*)

u s b f g l

Special Relay Area 1, 2

 

 

or

 

m d e c

(Word contents)

 

 

0…511

 

 

Link Relay Area

LR

Discrete

LR0:00...LR63:15

0, 1

 

(Bit status)

 

 

 

 

 

Link Relay Area

LR

Integer

LR0... LR63

(*)

 

(Word contents)

 

 

 

 

 

Holding Relay Area

HR

Discrete

HR0:00... HR99:15

0, 1

 

(Bit status)

 

 

 

 

 

Holding Relay Area

HR

Integer

HR0... HR99

(*)

u s b f g l

(Word contents)

 

 

 

 

m d e c

Auxiliary Relay Area

AR

Discrete

AR0:00... AR27:15

0, 1

 

(Bit status)

 

 

 

 

 

Auxiliary Relay Area

AR

Integer

AR0... AR27

(*)

u s b f g l

(Word contents)

 

 

 

 

m d e c

 

 

 

 

 

 

Timer/Counter Area

TC

Discrete

TC0... TC511

0, 1

 

Completion Flag(****)

 

 

 

 

 

Timer/Counter Area

PV

Integer

PV0... PV511

(*)

u s b f g l

(PV)

 

 

 

 

m d e c

Data Memory Area

DM

Discrete

DM0:00...

0, 1

 

(Bit status)(**)

 

 

DM9999:15

 

 

Data Memory Area

DM

Integer

DM0...

(*)

u s b f g l

(Word contents)(**)

 

 

DM9999

 

m d e c

Extended Data Memory

EM

Discrete

EM0:00...

0, 1

 

Area (Bit status)(***)

 

 

EM6143:15

 

 

Extended Data Memory

EM

Integer

EM0... EM6143

(*)

u s b f g l

Area Word contents(***)

 

 

 

 

m d e c

 

 

 

 

 

 

Item/point names, corresponding to Internal Relay/Special Relay Area may be without prefix.

(*)Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U" ("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default value range for Integer Tag Type is unsigned integer.

(**) Memory area range DM7000…DM9999 is supported o nly if Expansion DM Area is allocated on the PLC.

(***) Current bank only (Memory Area code 98).