Omron DR 170 14 manual Klinkmann Automation Omron Ethernet DAServer

Models: DR 170 14

1 67
Download 67 pages 16.17 Kb
Page 61
Image 61

Klinkmann Automation Omron Ethernet DAServer

59

 

 

 

operation manual)

 

 

 

 

 

 

 

04

Node number setting

Make sure the node

DASProtFail

 

 

error.

number is within

 

 

 

 

specified range and that

 

 

 

 

there are no duplicate

 

 

 

 

node numbers.

 

 

 

 

 

 

04: Not

01

An undefined

Check the command

DASProtFail

executable

 

command has been

code and be sure code

 

 

 

used, or short frame (4

is supported by Unit to

 

 

 

bytes) is being used for

which command is

 

 

 

FINS header frame.

sent.(*)

 

 

 

 

 

 

05: Routing

01

Destination node

Set the remote PLC in

DASProtFail

error

 

number is not set in the

the routing tables.

 

 

 

routing tables.

 

 

 

 

 

 

 

 

02

Routing tables aren't

Set the the routing

DASProtFail

 

 

registered.

tables at the relay nodes

 

 

 

 

and remote node.

 

 

 

 

 

 

 

03

Routing table error.

Set the the routing

DASProtFail

 

 

 

tables correctly.

 

 

 

 

 

 

 

04

The maximum number

Redesign the network to

DASProtFail

 

 

of relay nodes (2) was

reduce number of relay

 

 

 

exceeded in the

nodes.

 

 

 

command.

 

 

 

 

 

 

 

10:

01

The command is longer

Check the command

DASProtFail

Command

 

than the max.

format and set it

 

format error

 

permissible length.

correctly.(*)

 

 

 

 

 

 

 

02

The command is

Check the command

DASProtFail

 

 

shorter than the min.

format and set it

 

 

 

permissible length.

correctly.(*)

 

 

 

 

 

 

 

03

The designated

Check the number of

DASProtFail

 

 

number of data items

items and data and

 

 

 

differs from the actual

make sure that they

 

 

 

number.

agree.(*)

 

 

 

 

 

 

05

11:00

Parameter error

An incorrect header has been used. (Data for another node was received. Attempt was made to send response to broadcast address)

The parameter in the command data were incorrect or the

Check the header parameters in the command and be sure the correct command format is used.(*)

Check the parameters and be sure the socket number is between 1

DASProtFail

DASProtFail

Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3

17014m13

Page 61
Image 61
Omron DR 170 14 manual Klinkmann Automation Omron Ethernet DAServer