![](/images/new-backgrounds/1187124/187124121x1.webp)
Klinkmann Automation Omron Ethernet DAServer | 59 |
|
|
| operation manual) |
|
|
|
|
|
|
| 04 | Node number setting | Make sure the node | DASProtFail |
|
| error. | number is within |
|
|
|
| specified range and that |
|
|
|
| there are no duplicate |
|
|
|
| node numbers. |
|
|
|
|
|
|
04: Not | 01 | An undefined | Check the command | DASProtFail |
executable |
| command has been | code and be sure code |
|
|
| used, or short frame (4 | is supported by Unit to |
|
|
| bytes) is being used for | which command is |
|
|
| FINS header frame. | sent.(*) |
|
|
|
|
|
|
05: Routing | 01 | Destination node | Set the remote PLC in | DASProtFail |
error |
| number is not set in the | the routing tables. |
|
|
| routing tables. |
|
|
|
|
|
|
|
| 02 | Routing tables aren't | Set the the routing | DASProtFail |
|
| registered. | tables at the relay nodes |
|
|
|
| and remote node. |
|
|
|
|
|
|
| 03 | Routing table error. | Set the the routing | DASProtFail |
|
|
| tables correctly. |
|
|
|
|
|
|
| 04 | The maximum number | Redesign the network to | DASProtFail |
|
| of relay nodes (2) was | reduce number of relay |
|
|
| exceeded in the | nodes. |
|
|
| command. |
|
|
|
|
|
|
|
10: | 01 | The command is longer | Check the command | DASProtFail |
Command |
| than the max. | format and set it |
|
format error |
| permissible length. | correctly.(*) |
|
|
|
|
|
|
| 02 | The command is | Check the command | DASProtFail |
|
| shorter than the min. | format and set it |
|
|
| permissible length. | correctly.(*) |
|
|
|
|
|
|
| 03 | The designated | Check the number of | DASProtFail |
|
| number of data items | items and data and |
|
|
| differs from the actual | make sure that they |
|
|
| number. | agree.(*) |
|
|
|
|
|
|
05
11:00
Parameter error
An incorrect header has been used. (Data for another node was received. Attempt was made to send response to broadcast address)
The parameter in the command data were incorrect or the
Check the header parameters in the command and be sure the correct command format is used.(*)
Check the parameters and be sure the socket number is between 1
DASProtFail
DASProtFail
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3 | 17014m13 |