DAServer Device-Group-Specific System Items

The following system items refer to specific information regarding device groups that have been configured in the DAServer.

System Item

Type/

Description

Values

Name

Access

 

 

 

Rights

 

 

$SYS$UpdateInterval

DWord/

Used to access the currently

RANGE:

 

ReadWrite

set update interval. It is the

1…2147483647

 

 

current update interval of the

0: Topic inactive,

 

 

device group in milliseconds.

no items are

 

 

A client can poke new values

updated. Data

 

 

into this item.

acquisition is

 

 

The value of zero indicates

stopped.

 

 

that no non-system items on

>0: Expected

 

 

that topic are updated (data

updated interval

 

 

for these items are not

for the set of all

 

 

acquired from the device).

items in the

 

 

 

device group.

$SYS$MaxInterval

DWord/

Used to access the currently

RANGE:

 

Read

measured maximum update

0…2147483647

 

 

interval in milliseconds of all

0: If update

 

 

items of the corresponding

interval is 0 or if

 

 

device group. This item is

the status is

 

 

read-only. The value of the

false.

 

 

slowest item is displayed.

>0: Measured

 

 

 

update interval

$SYS$WriteComplete

Integer/

Used to access the state of

RANGE: -1, 0, 1

 

ReadWrite

pending write activities on the

1: Write

 

 

corresponding device group.

 

 

On device group creation

complete (no

 

 

(adding items to an OPC

writes are

 

 

group), the value of this

pending – initial

 

 

system item is initially 1,

state).

 

 

indicating all write activities

0: Writes are

 

 

are complete – no pokes are

pending.

 

 

pending.

-1: Writes

 

 

If values are poked into any

completed with

 

 

items of the device group, the

errors.

 

 

value of this item changes to

 

 

 

0, indicating write activity is

 

 

 

currently in progress.

 

 

 

If the server has completed all

 

 

 

write activities, the value of

 

 

 

this item changes to 1 if all

 

 

 

pokes were successful or to -1

 

 

 

if at least one poke has failed.

 

 

 

If the value of this item is not

 

 

 

zero, the client can poke 1 or -

 

 

 

1 to it (poke a 1 to clear errors,

 

Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3