Klinkmann Automation Omron Ethernet DAServer 60
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3 17014m13
UDP/TCP socket
number was not within
the proper range
and 8.
01 An incorrect memory
area or unavailable
expansion mem. area
has been used.
Check the command’s
memory area code.
Check whether right
controller type
configured in DAServer.
Check whether controller
does has polled memory
areas.
DASProtFail
03 The first address is in
inaccessible area. Set the first word that is
in an accessible area.
Check whether right
controller type
configured in DAServer.
DASProtFail
22: Status
error 0F The same socket
service is already in
progress at the
specified socket
number.
Use the socket status
flag in PC memory to be
sure that socket service
has finished before
starting services again.
(Error deals with
Ethernet communication
programming in PLC’s
user program).
DASProtFail
10 The specified socket is
not open. Open the socket. DASProtFail
23:
Environmen
t error
05 IP address conversion
failed. Check the IP address
and subnet mask in the
System Setup and be
sure that settings are
correct.
DASProtFail
07 IP address conversion
is set for automatic
conversion only.
Check the mode settings
for System Setup. This
error will be generated
for the READ IP
ADDRESS command
only.
DASProtFail
25: Unit
error 03 I/O setting error. (The
I/O table differs from
the actual Unit
configuration).
Either change the actual
configuration to match
the registered one or
generate I/O table again.
DASProtFail
05 CPU bus error. (An
error occurred during Check the Units and
cable connection and DASProtFail