4-2SectionProgramming Console Operations
48
Program Read then Monitor When a program address is being displayed, the status of the bit or word in that
address can be monitored by pressing the MONTR Key.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
2. Input the desired program address and press the Down Arrow Key.
C2A0A0↓00200READ
TIM 000
3. Press the MONTR Key to begin monitoring.
MONTR T000
1234
If the status of a bit is being monitored, that bit’s status can be changed using
the Force Set/Reset operation. Refer to page 56 for details.
If the status of a word is being monitored, that word’s value can be changed
using the Hexadecimal/BCD Data Modification operation. Refer to page 53
for details.
4. Press the CLR Key to end monitoring.
CLR 00200
TIM 000
Bit Monitor Follow the procedure below to monitor the status of a particular bit.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
2. Input the bit address of the desired bit and press the MONTR Key.
SHIFT CONT
#
B1MONTR 00001
^ ON
The Up or Down Arrow Key can be pressed to display the status of the pre-
vious or next bit.
The displayed bit’s status can be changed using the Force Set/Reset opera-
tion. Refer to page 56 for details.
3. Press the CLR Key to end monitoring.
CLR 00000
CONT 00001
Word Monitor Follow the procedure below to monitor the status of a particular word.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
2. Input the word address of the desired word.
SHIFT CH
*DM LR
*EM B100000
CHANNEL LR 01
3. Press the MONTR Key to begin monitoring.
MONTR cL01
FFFF
The Up or Down Arrow Key can be pressed to display the status of the pre-
vious or next word.
The displayed word’s status can be changed using the Hexadecimal/BCD
Data Modification operation. Refer to page 53 for details.
4. Press the CLR Key to end monitoring.
CLR 00000
CHANNEL LR 01
The status of up to six bits and words can be monitored simultaneously, although
only three can be shown on the display at any one time.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
Multiple Address
Monitoring